5.3 UC20-SL2000-EC
Up to 64 active u-remote modules can be connected via the
u-remote system bus to the UC20-SL2000-EC controller. The
controller has two Ethernet connections for integration into
the existing network architecture or HMI connections.
The controller can be congured as a EtherCAT master.
The u-control station can be congured and parametrised
and controlling applications can be programmed using the
engineering tool u-create studio (according to IEC61131-3,
additional programming languages: C and C++)
The station’s main power supply is integrated into the con-
troller. Power is supplied via two 4-pole connectors, separat-
ed into the input and output current paths.
Controller UC20-SL2000-EC (Order No. 2674520000)
Status indicators
PWR
SF
BF
MT
AC
1
2
3
4
1
2
3
4
RUN/STOP
L/A X1
L/A X2
3
4
X1
X2
LEDstatusindicatorsUC20-SL2000-EC,forerrormessagesseeChapter12
PWR Power LED green: supply voltage present, rmware is
running
SF System failure red: system bus failure
BF Bus failure red: eld bus failure
MT Maintenance yellow: communication error with module
RUN Controller status green: application running
greenashing: application stopped
yellow: operating system running
yellowashing: system update running
red: serious system failure
L/A X1 Connection/
activity
green: connection of controller connection 1
with an additional eld device
green/yellowashing: data being ex-
changed on connection1
L/A X2 Connection/
activity
green: connection of controller connection 2
with an additional eld device
green/yellowashing: data being ex-
changed on connection2