User Documentation
Configuration
54
Tab "Basic Configuration"
Like for all configuration windows, the structure for EtherCAT slave devices
is split into three parts "General", "Info", and "Advanced". For normal opera-
tion parameter of part "Advanced" need not to be changed. Furthermore, the
area "General" is also split into the areas "Device Identification", "Distributed
Clock" and "Sync".
Fig.15-31: Part "General"
General
Element Meaning
Timing mode
● Cycle Time: Insert a cycle time in μs. The value must be a multiple
of the masters cycle time.
● Master: Cycle time of the master is adopted.
● Task: Selection of a configured Task
● Reduction: Regarding to the cycle time of the master, those of the
configuring device will be slowed by the selected factor.
Fast Control Activates fast control for in-/outputs of the module
Expert Settings
Activates expert settings. If activated, further tabs ("Expert Prozess
Data") are available.
Availability
EtherCAT slave devices can be configured so that they do not always
have to be physically present in order to be able to perform tests. The fol-
lowing selection options are available for that:
● Mandatory: The availability of the device is mandatory
● Optional: In the setting, the operation with and without existing slave
devices possible, while the device is actually controlled if it is
present.
Simulation mode
● Not simulated: Device is connected and controlled.
● Simulated (slave not plugged in): The interfaces to slave devices are
controlled in the simulation.
● Simulated with hardware (slave plugged in): In this case, the slave
device is not controlled even though it is present. This allows to still
perform tests with a complete structure without the risk to control the
connected devices.