User Documentation
TERMSERIES TIMER
Type Order-No.
TRS T 24VDC 1CO M3 2639560000
Ordering data
T = Time factor x Time range (nal value) | *LED Or = LED Orange | *LED Gn = LED Green
Timing functions
A1 / A2
15 / 18
T
On Delay
A1 / A2
Blinker
15 / 18
LED Gn*
TTTT
A1 / A2
15 / 18
T
One Shot
LED Or*
LED Or*
LED Gn
*
LED Or*
LED Gn*
*LED Or = LED Orange
LED Gn = LED Green
0,5s
t<T
A1 / A2
15 / 18
T
On Delay
A1 / A2
Blinker
15 / 18
LED Gn*
TTTT
A1 / A2
15 / 18
T
One Shot
LED Or*
LED Or*
LED Gn*
LED Or*
LED Gn*
*LED Or = LED Orange
LED Gn = LED Green
0,5s
t<T
On Delay
When the supply voltage A1/A2 is applied, the
set time T begins to run. When the time has
passed, the output relay 15/18 switches into on-
position. This state remains active until the sup-
ply voltage is interrupted. If the supply voltage is
interrupted before time T has passed, the already
run time is deleted and restarted with the next
application of supply voltage.
One Shot
When the supply voltage A1/A2 is applied, the
set time T runs. After the time T has passed, the
output relay 15/18 switches into on-position for
0.5 s. After 0.5 s the output relay switches into
off-position. The time function is not restarted
until the next time the supply voltage is applied.
Blinker
When the supply voltage A1/A2 is applied, the
output relay 15/18 switches into on-position.
After the set pulse time T has passed, the output
relay switches into off-position. After the pause
time T has passed, the output relay switches
into on-position again. The output relay is acti-
vated for the set time until the supply voltage is
interrupted. (T=pulse time=pause time)
A1 / A2
15 / 18
T
On Delay
A1 / A2
Blinker
15 / 18
LED Gn
*
TTTT
A1 / A2
15 / 18
T
One Shot
LED Or*
LED Or*
LED Gn*
LED Or*
LED Gn*
*LED Or = LED Orange
LED Gn = LED Green
0,5s
t<T
Function DIP switch
Mode = On Delay
Time range = 0.1...1 s
Time factor = 0.7
1 2 3 4 5 6 7 8
Example: DIP switch adjustment for a on delay of 0.7 s
= ON (DIP switch position)