User Documentation
5
Scope and standards
1438130000/02/07-2018
1.1 Scope
This safety manual applies to SIL3 relays from
Weidmüller‘s SAFESERIES for the following items
produced after 11/2012:
SCS 24VDC P2SIL3ES 1319280000
SIL3 relays in the SCS 24VDC P2SIL3ES series
from
Weidmüller Interface GmbH & Co KG
Klingenbergstraße 16
32758 Detmold
Germany
have been certied by
TÜV NORD CERT GmbH
Certication Body
Maschinery
Notied Body 0044
Langemarckstr. 20
45141 Essen
Germany
according to EN 61508 SIL3. They are certied
as “EC type-examination” for use in “low demand
mode” and “high demand mode” systems.
CerticateRegistrationNo:
44 205 12 413770-001
1 Scope and standards
1.2 Abbreviations
SafetyIntegrityLevel(SIL):
Four discrete levels (SIL1 to SIL4). The higher the
SIL of a safety-related system, the lower the prob-
ability that it will not perform the required safety
functions.
AverageProbabilityofFailureonDemand
(PFD
avg
):
Average probability of failure of a safety function
working in low demand mode of operation.
ProbabilityofFailureperHour(PFH):
Average probability of failure of a safety function
working in high demand or continuous mode of op-
eration.
SafeFailureFraction(SFF):
Percentage part of safe failures and dangerous de-
tected failures of a safety function or a sub-system
related to all failures.
HardwareFaultTolerance(HFT):
HFT = n means, that n+1 faults could cause a loss of
the safety function.
Lowdemandmodeofoperation:
Frequency of demands on a safety-related system
no greater than one per year and no greater than
twice the proof-test frequency.
Highdemandorcontinuousmodeofoperation:
Frequency of demands on a safety-related system
greater than one per year or greater than twice the
proof-test frequency.
DevicetypeA(simplesubsystem):
The failure modes of all constituent components are
well dened and the behaviour under fault conditions
can be completely determined.