User Documentation

13
Periodic inspections
1438130000/02/07-2018
5.1 Functionalcheck
Functional testing is done in three steps according to the following tables.
5.1.1 “Reset”functionaltest
Input voltage: 24 V DC
Connection: S33/S34
Reset Monitoring Indication Output
Acknowl-
edgement
S33/S34 S11/S12 S21/S22 LED K1 LED K2 13/14 23/24 31/32
0→1→0 open open OFF OFF open open closed
0→1→0 closed open OFF OFF open open closed
0→1→0 open closed OFF OFF open open closed
0→1→0 closed closed ON ON closed closed open
5.1.2 “AutoStart”functionaltest
Input voltage: 24 V DC
Connection: S33/S35
Control
input
Monitoring Indication Output
Acknowl-
edgement
A1/A2 S11/S12 S21/S22 LED K1 LED K2 13/14 23/24 31/32
0→1 open open OFF OFF open open closed
0→1 closed open OFF OFF open open closed
0→1 open closed OFF OFF open open closed
0→1 closed closed ON ON closed closed open
5.1.3 “Monitoring”functionaltest
Input voltage: 24 V DC
Connection: S33/S35
Test step
Monitoring Indication Output
Acknowl-
edgement
S11/S12 S21/S22 LED K1 LED K2 13/14 23/24 31/32
1. closed closed ON ON closed closed open
2. open closed OFF ON open open closed
3. closed closed OFF ON open open closed
4. closed open OFF OFF open open closed
5. closed closed ON ON closed closed open
6. open open OFF OFF open open closed