User Documentation
10 2555600000/02/05-2018
Proof test
5.1 Functional testing
A1
+
-
I
1
U
1
A1 A1 A2 A2
A1 A2A2A1
SAFESERIES
FUSE
T5AL250V
RELAY
OUTPUT
SCS 24VDC
P1SIL3DS I
2500980000
T1
13 14 15
T2
13 14 T1 15
T2
A2
+
-
U
2
I
2
R
A
B
Functional testing A B
Internal fuse and relay contact circuit 13 15
Contact set 1 14 T1
Contact set 2 T1 T2
Contact set 3 T2 15
Input circuit active
• U
1
= 24 V DC, input voltage at the connection
terminals A1(+) and A2(-) is switched on
○ current consumption is I
1
= 45...55 mA (am-
meter A1)
○ the “RELAY OUTPUT” LED lights up
○ Functional testing of internal fuse and relay
contact circuit:
the connection terminals 13 and 15 are elec-
trically connected, current consumption is
I
2
= 10 mA (ammeter A2)
Input circuit inactive
• U
1
= 0 V DC, input voltage at the connection ter-
minals A1(+) and A2(-) is switched o
○ current consumption is I
1
= 0 mA (amme-
ter A1)
○ the “RELAY OUTPUT” LED does not light up
○ Functional testing contact set 1:
the connection terminals 14 and T1 are not
electrically connected, current consumption is
I
2
= 0 mA (ammeter A2)
○ Functional testing contact set 2:
the connection terminals T1 and T2 are not
electrically connected, current consumption is
I
2
= 0 mA (ammeter A2)
○ Functional testing contact set 3:
the connection terminals T2 and 15 are not
electrically connected, current consumption is
I
2
= 0 mA (ammeter A2)
Dimensioning recommendation:
U
2
= 12 V DC
R = 1200 Ω