Approval/Certificate/Document of Conformity

K£MA
i(
Mounting instructions
The series terminal blocks are suitable for use in enclosures in atmospheres with combustible
gases and combustible dust. For combustible gases these enclosures must satisfy the
requirements according to EN 50014 and EN 50019. For combustible dust these enclosures
must satisfy the requirements according to prEN 50281-1-1 .
At ambient temperatures from -50
DC
up to +40
DC
and based on the self-heating, if used at
the above mentioned rated current, the series terminal blocks may be used in electrical
apparatus, e.g. junction and connection boxes, for temperature class T6.
If mounted in apparatus of temperature classes T1 up to T5, the highest temperature of the
insulating material Wemid shall not exceed the value of 100
DC
and the insulating material
PA 66 shall not exceed the value of 80
DC.
Regarding the use of cover sheets, separating plates and end supports the instructions of the
manufacturer must be followed.
In combination with other terminal blocks series and sizes and if other accessories are used
the applicable creepage distances and clearances shall be met.
If smaller cross sections as the rated cross section are used, the belonging lower current has
to be laid down in the EC-Type Examination Certificate of the complete apparatus.
Routine test
According to EN 50019, Clause 7.lob in combination with Clause 6.1, a dielectric strength
test has to be carried out.
Test documentation
sioned
1. Description (10 pages)
2. Drawing No. 422359 Rev. 1
422361 Rev. 2
415307 Rev. 6
405487 Rev.14
403346 Rev. 6
402981 Rev. 3
424194 Rev. 1
424196 Rev. 1
415308 Rev. 5
303342 Rev.23
403343 Rev. 7
402977 Rev. 3
405620 Rev. 9
424740
415309 Rev. 5
402978 Rev. 3
404005 Rev.10
403957 Rev. 8
405446 Rev. 3
23.07.1997
23.07.1997
Page 3/4