When installing the shielding connection, observe the following:
   Remove the sheath of the PROFINET cable only to the 
extent required for the connection. The PROFINET cable 
is sensitive to mechanical loads in the area where the 
sheath was removed.
   Make sure you don't damage the shielding when you 
strip the sheath off the PROFINET cable.
   Do not use the shielding connection as strain-relief. 
This would impair the contact between the shielding 
and the equipotential bonding. Exception: installation 
material specially designed for this purpose.