User Documentation
Planning
2053260000/05/2015
31
2.9.4  Connect the shielding with the equipotential bonding.
The shielding is an important part of the PROFINET copper cable.
This shielding protects the data wires in the cable against electromagnetic 
interference.
For the shielding to perform this function, it must be connected to the 
equipotential bonding of the system.
Connect the shielding of the PROFINET copper cables to the equipotential 
bonding at the following points:
•  At PROFINET devices
   The equipotential bonding is implemented using the 
appropriate connector and by connecting the cable to 
the equipotential busbar.
•  At the cabinet entry
   Connect the shielding of the PROFINET cable to the 
equipotential bonding at the entry to the control 
cabinet. This means that interference that acts on 
the PROFINET cable outside the control cabinet is 
prevented from being directed into the cabinet.
   To achieve this, mount an equipotential busbar behind 
the strain-relief on the cabinet entry.