User Documentation
Planning
2053260000/05/2015
29
    Connect the installation surfaces (e.g., top-hat rails) to 
the equipotential bonding.
   Connect the system's equipotential bonding as often 
as possible with the building's equipotential bonding.
   In the case of painted parts, remove the paint from 
the connection point prior to connecting.
   After installation, protect exposed connecting points 
against corrosion, using zinc paint or enamel.
   Protect the equipotential bonding against corrosion. 
One option, is to paint the contact points.
   Use secure screw or clamp connections. Under no 
circumstances should the connection come loose on 
its own.
   Make sure to use wire-end ferrules or cable lugs 
for exible equipotential bonding cables. Under no 
circumstances should the cable ends be tin-plated (as 
this is no longer permitted)!










