For the earth connection of the PROFINET devices, use copper cable
with a corresponding cross-section (> 2.5 mm²). As a rule, the earthing cable has 
a green-and-yellow insulation. In some countries the green-and-yellow marking is 
a regulation (in the USA only green).
The functional earth is identied by the following symbol:
g
2.9.3  Equipotential bonding
Equipotential bonding ensures that the earth potential is equal throughout 
the system. This means no compensating currents ow over the shielding of 
the PROFINET cable. Use copper cable or galvanised earthing strips for the 
equipotential bonding in the system and between the system parts.
   Connect large areas of the equipotential bonding with 
the earth terminal or earth bus.
   Connect all shields and earthing connections (if any). As 
the name indicates, the equipotential bonding ensures 
that the potential is equal in all parts of the system. This 
prevents compensating currents from owing over the 
shielding of the PROFINET cable.