Since the protective earth is part of the general electrical system, it will not 
be described in any more detail in this document. However, the applicable 
regulations are to be observed in each case!
   Note 
Some PROFINET devices also have a connection for the protective 
earth. In particular, these are PROFINET devices that have an additional 
power supply with a higher voltage. Connect the protective earth in 
accordance with the applicable regulations.
2.9.2  Functional earthing
The functional earth is used to discharge EMC interference to earth. This 
increases the interference immunity of the data transmission. The functional earth 
is used to earth the cable shields and housing of devices in order to discharge 
interference to earth.
   Manufacturer's  instructions 
Read the manufacturer's documentation. The manufacturer information 
gives you details about how you need to connect the PROFINET nodes 
in terms of earthing and equipotential bonding
Some PROFINET devices have a connection terminal for the functional earth. 
The connection terminal is marked with the symbol for the functional earth. 
To connect the connection terminal of the PROFINET devices to the functional 
earth of the system, use a cable that has the shortest possible length and a large 
cross-section. In many cases the entire metallic structure of the system is used 
as functional earth. With other devices, the functional earth is implemented by 
means of the installation fastening. Therefore, also connect the system's top-hat 
rails to the functional earth.