User Documentation
2053260000/05/201526
Planning
2.9  Earthing and equipotential bonding
A good earthing system and good equipotential bonding system are very 
important for the electrical interference immunity of PROFINET networks. Earth 
the PROFINET cable shields on both sides, i.e. on each of the connected devices, 
in order to reduce the effects of electromagnetic interference. The equipotential 
bonding ensures that the earth potential is equal throughout the entire 
PROFINET network. This protects against equipotential bonding currents that 
could otherwise ow over the shielding of the PROFINET cable. The following 
explanations provide basic information on installing the earthing and the 
equipotential bonding.
   Manufacturer's  instructions 
Please read the information provided by the manufacturer. 
This information provides you with important details on how to 
best connect the PROFINET stations with the earthing and the 
equipotential bonding.
2.9.1  Protective earth
The protective earth is essentially used to protect people against an electric
shock in the event of a fault. However, the protective earth also protects
machines and installations against damage from faults. Metallic conductive 
parts, such as frames, control cabinets or plant parts must be connected to the 
protective earth. The conductor used must be measured so that it can discharge 
residual current in the event of a fault.
The protective earth is designated by the following symbol:
h 