   If the cables are routed in metallic cable conduits, the 
conduits can be positioned right next to one another.
   If there is just one shared metallic cable conduit 
available for all categories, the spacing stated in Table 
3.1 should be observed. If there isn’t enough space, 
the various cable categories must be isolated using 
metallic partitions. The partitions must be connected 
to the conduit over large areas, ensuring good 
conductivity.
   If cables of different categories cross, they should 
be crossed at right angles. Do not route cables of 
different categories over long distances in parallel.
 (Source:PROFINETassemblyguideline,version1.0,January2009)