User Documentation
Title: PROtop IO-Link Register Description
2019.11.29, Page 7/17
DocVersion: 1.1
3.3 Non-cyclical I/O data of PROtop IO-LINK
3.3.1 Parameters for PROtop IO-LINK
Table 3: Parameters for PROtop IO-LINK
Name
Type
Length
Access
Index
Comment/ Description
PROtop Over Voltage Peaks Coun-
ter
U16
2
bytes
R
257
Number of “PROtop - Over Voltage Peaks
Failed” events since production of the PROtop.
PROtop Device Temperature
S16
2
bytes
R
260
Internal temperature (heat sink at rectifier of
PROtop) in cC° (1000 = 10.00°C).
PROtop Device Temperature
>100°C Counter
U16
2
bytes
R
261
Number of “PROtop - Device Temperature
>100°C” events since production of the PROtop.
PROtop Device Temperature
>110°C Counter
U16
2
bytes
R
262
Number of “PROtop - Device Temperature
>110°C” events since production of the PROtop.
PROtop Device Type
String
[32]
32
bytes
R
268
Product (type) name of PROtop.
PROtop Device Order Nr
String
[10]
10
bytes
R
269
Order number of PROtop.
PROtop Device Serial Nr
String
[15]
15
bytes
R
270
Serial number of PROtop.
PROtop Device HW Version
String
[8]
8
bytes
R
272
Hardware version number of the PROtop
PROtop Device SW Version
String
[8]
8
bytes
R
273
Software version number of the PROtop
PROtop Operation Hours Since
Production Counter
U32
4
bytes
R
274
The operating hours since production of the
PROtop.
PROtop Device State
U8
bit-
map,
record
1 byte
R
275
This register shows the internal state of the
PROtop device. The bits are defined as the
following:
bit 0: FAILURE
bit 2: OUT OF SPECIFICATION
bit 3: MAINTANANCE REQUIRED,
bit 4: PREWARNING
bit 5: CONFIGURATION DOWN LOAD
PROtop Device Tag
Byte
[16]
16
bytes
RW
276
The device tag is settable to define a unique
name for the device in the automation plant.
Default value = "WeidmuellerInter".
PROtop Rated Value Voltage Out-
put
S32
4
bytes
RW
282
Set the Voltage in dV on DC- Output (after O-
ring MOSFET) to the transferred rated value.
Step width: 30mV
Range: 40% of U
nom
to U
max
)
Default value = U
nom
This parameter is only valid, if “PROtop Configu-
ration Select” = 0x01. Otherwise the “PROtop
Rated Value Voltage Output” is configured by
the Poti.
The parameter is active immediately.
Without further action, the value is reset to de-
fault value after restart of Power Supply.
To store this value after a Power Supply Reset
see “PROtop Save Rated Voltage Output Value