User Documentation
Title: PROtop IO-Link Register Description
2019.11.29, Page 5/17
DocVersion: 1.1
3 Process data and parameter
3.1 Process data in
Table 1: Process data in for PROtop IO-LINK
Parameter
Type
Bit-Offset
Length
[Bit]
Comment/ Description
PROtop - Output Voltage
INT16
40
16
Output voltage value in cV (1000 = 10.00V) on DC- Output
after O-ring MOSFET (on terminal).
PROtop - O-Ring Voltage
INT16
24
16
Output voltage value in cV (1000 = 10.00V) on DC- Output
before O-ring MOSFET.
PROtop - Output Current
INT16
8
16
Output current in cA (1000 = 10.00A) on DC- Output
PROtop - DI State
Bool
7
1
Get Status of Digital Input
0 = false (V
in
< 5V)
1 = true (V
in
> 15V)
PROtop - Relay State
Bool
6
1
Get State of Relay Output
0 = deenergized
1 = energized
PROtop - DCL Active State
Bool
5
1
0 = DCL event is not active on DC- Output
1 = DCL event is active on DC- Output
PROtop - Overload 150 Active
State
Bool
4
1
0 = load current on DC- Output is lower than 150% of I
nom
1 = load current on DC- Output is higher than 150% of I
nom
PROtop - Overload 110 Active
State
Bool
3
1
0 = load current on DC- Output is lower than 110% of I
nom
1 = load current on DC- Output is higher than 110% of I
nom
PROtop - Short Circuit Switch Off
State
Bool
2
1
0 = DC / DC conversion and O-ring MOSFET DC Output is
active
1 = DC / DC conversion and O-ring MOSFET DC Output is
switched off, because of a short circuit
PROtop - Load Prewarning State
Bool
1
1
0 = load current on DC- Output is lower than “PROtop Load
Prewarning Value”, which is 90% of I
nom
.
1 = load current on DC- Output is higher than “PROtop Load
Prewarning Value”, which is 90% of I
nom
.
PROtop - Short Circuit Active State
Bool
0
1
0 = Short Circuit on DC Output
1 = No Short Circuit on DC Output
Padding
0
padding
Total size PD-IN
56
7 Bytes