User Documentation
Title: PROtop IO-Link Register Description
2019.11.29, Page 4/17
DocVersion: 1.1
2 Communication via IO-LINK
2.1 Configuration of PRO TOP IO-LINK system
For the configuration of PROtop IO-LINK the following points should be note:
➔ The Function “Data Storage” is not supported and must be disabled in the engineering tool!
➔ Writing an invalid value into a writeable parameter register does not evoke an error. To assure that a
value has been accepted, it is necessary to read back the register and verify the content.