User Documentation

Title: PROtop IO-Link Register Description
2019.11.29, Page 13/17
Table 3: Parameters for PROtop IO-LINK
Name
Type
Length
Access
Index
Comment/ Description
CIOL Device Temperature <-25°C
Counter
U16
2
bytes
R
343
Number of external temperature <-25°C since
production is counted at Communication IO-
LINK device
CIOL Device Temperature <-40°C
Counter
U16
2
bytes
R
344
Number of external temperature <-40°C since
production is counted at Communication IO-
LINK device
CIOL Power Down Cycles Counter
U16
2
bytes
R
346
Number of Power Down Cycles since production
of Communication IO-LINK device.
Combi Device Failure State
Bool
1 byte
R
351
Shows a combined device failure state.
0 = OK
1 = Failure at PROtop or Communication IO-
LINK device.
Combi Device ID Switch Changed
State
Bool
1 byte
R
352
Signals a change of the ID Switch within opera-
tion.
0 = No change
1 = Change