User Documentation
Title: PROtop IO-Link Register Description
2019.11.29, Page 12/17
DocVersion: 1.1
Table 3: Parameters for PROtop IO-LINK
Name
Type
Length
Access
Index
Comment/ Description
PROtop DC Not OK Counter
U16
2
bytes
R
321
Number of “PROtop - DC not OK” events since
production of the PROtop.
PROtop DC Lower Threshold
float
4
bytes
R,
W
322
This register defines the Lower Threshold for the
“DC not OK” detection. It is given in percent of
configured output.
Max Value: 25 %
Default Value: Value: 15 %
This parameter is only valid, if “PROtop Configu-
ration Select” = 0x01. Otherwise the default
value is used.
The parameter is active after restart.
PROtop DC Upper Threshold
float
4
bytes
R,
W
323
This register defines the Upper Threshold for the
“DC not OK” detection. It is given in percent of
configured output.
Max Value: 25 %
Default Value: Value: 10 %
This parameter is only valid, if “PROtop Configu-
ration Select” = 0x01. Otherwise the default
value is used.
The parameter is active after restart.
PROtop DI Pull Up Select
Bool
1 byte
R,
W
324
Switches on/off Pull Up Resistor at Digital Input
of PROtop
0 = pull up resistor is active
1 = pull up resistor is not active;
Default value = 0
This parameter is only valid, if
CONFIGURATION_SEL = 0x01. Otherwise the
default value is used.
The parameter is active after restart.
CIOL Device Type
String
[32]
32
bytes
R
327
Product (type) name of Communication IO-LINK
device
CIOL Device Order Nr
String
[10]
10
bytes
R
328
Order number of Communication IO-LINK de-
vice.
CIOL Device Serial Nr
String
[15]
15
bytes
R
329
Serial number of Communication IO-LINK de-
vice.
CIOL Device HW Version
String
[8]
8
bytes
R
331
Hardware version number of Communication IO-
LINK device
CIOL Device SW Version
String
[8]
8
bytes
R
332
Software version number of Communication IO-
LINK device
CIOL Device DVN Version
String
[8]
8
bytes
R
333
DVN of Communication IO-LINK device
CIOL Operation Hours Since Pro-
duction Counter
U32
4
bytes
R
334
The operating hours since production of Com-
munication IO-LINK device
CIOL Device Temperature
S16
2
bytes
R
340
External temperature of Communication IO-LINK
device in cC° (1000 = 10.00°C).
CIOL Device Temperature >60°C
Counter
U16
2
bytes
R
341
Number of external temperature > 60°C since
production is counted at Communication IO-
LINK device
CIOL Device Temperature >70°C
Counter
U16
2
bytes
R
342
Number of external temperature > 70°C since
production is counted at Communication IO-
LINK device