User Documentation

Title: topGUARD IO-Link Register Description
2020.02.17, Page 7/21
released
TGD-ELM Short Circuit Switch Off
Bool
1
1
Event, if switched off (tripping) the DC-Output of corre-
sponding top Guard ELM
Condition: tripping of ELM regarding selected tripping
characteristic curve at Register “TGD-ELM Tripping Charac-
teristic Curve Select” and tripping current limit at register
“TGD-ELM Tripping Current Limit”.
TGD-ELM Device Failure
Bool
0
1
Event, if top Guard ELM detects any internal failure
Condition: Internal failure occurred
0: No failure
1: Failure
Padding
0
padding
Total size PD-IN per top Guard elec-
tronic load monitoring device
4
1/2 [Byte]
Total size PD-IN (limit is 32 Byte PD-In)
N × 4
N/2 [Byte]
4.2 Process data out
There is no data defined for “Process data out”.
4.3 Non-cyclical I/O data of topGuard IO-LINK
4.3.1 Parameters for topGuard IO-LINK
Data Storage function is not implemented until now!
We have three kinds of possible data sources and sinks:
- CIOL -> The PRO COM IO-LINK module
- FIM -> The TGD FIM-C module
- TGD-ELM -> The several TGD ELM-6, TGD ELM-12 or TGD ELM-4 CL2 electronic load monitoring
devices in the station.
For the TGD-ELM the non-string data is defined as an array, where the sub index of this array is the
address of corresponding electronic load monitoring device.
The String data is not sorted within arrays, they are accessed by their names.
Replace the “<N>” in the following overview with the address of the corresponding electronic load
monitoring device.
Table 2 Parameters for topGuard IO-LINK
Name
Type
Length
Access
Index
Data Source/Sink
Comment/ Description
TGD-ELM Over Voltage Peaks Counter [<N>]
U16
2 bytes
R
256
TGD
-
ELM
The number of Over Voltage peaks at
V
In
of the corresponding ELM device
since production.
TGD-ELM Under Voltage Peaks Counter
[<N>]
U16
2 bytes
R
257
TGD
-
ELM
The number of Under Voltage peaks at
V
In
of the corresponding ELM device
since production.