User Documentation

Title: topGUARD IO-Link Register Description
2020.02.17, Page 6/21
released
4 Process data and parameter
The topGUARD modules can be built up in a station with up to N < = 32 topGUARD electronic load monitor-
ing devices.
The process input data delivers an array of 4 Bit values, which represent the following states for each ELM
device.
- Bit 0: Device Failure
- Bit 1: Short Circuit Switch Off
- Bit 2: Load Pre-Warning
- Bit 3: Load Alarm Warning
The values are assigned to the addresses by the name of the process input data item, e.g. “Process Data In
Address 01” represents the states of the ELM device with the address 1.
4.1 Process data in
Table 1: Process data in for topGuard IO-LINK
No. of
top
Guard
Fuse
Parameter
Type
Bit-Off-
set
Length
[Bits]
Comment/ Description
N=31
TGD-ELM Load Alarm Warning
Bool
127
1
See below!
TGD-ELM Load Pre-Warning
Bool
126
1
See below!
TGD-ELM Short Circuit Switch Off
Bool
125
1
See below!
TGD-ELM Device Failure
Bool
124
1
See below!
….
TGD-ELM Load Alarm Warning
Bool
1
See below!
TGD-ELM Load Pre-Warning
Bool
1
See below!
TGD-ELM Short Circuit Switch Off
Bool
1
See below!
TGD-ELM Device Failure
Bool
1
See below!
N=2
TGD-ELM Load Alarm Warning
Bool
7
1
See below!
TGD-ELM Load Pre-Warning
Bool
6
1
See below!
TGD-ELM Short Circuit Switch Off
Bool
5
1
See below!
TGD-ELM Device Failure
Bool
4
1
See below!
N=1
TGD-ELM Load Alarm Warning
Bool
3
1
Event, if output current on DC-Output of corresponding top
Guard ELM is higher than present “TGD-ELM Load Alarm
Warning Value”.
Condition:
I
out
> TGD-ELM Load Alarm Warning Value
TGD-ELM Load Pre-Warning
Bool
2
1
Event, if output current on DC-Output of corresponding top
Guard ELM is higher than present “TGD-ELM Load Prewarn-
ing Value”
Condition:
I
out
> TGD-ELM Load Prewarning Value