User Documentation
Title: topGUARD IO-Link Register Description
2020.02.17, Page 21/21
DocVersion:
1.2
released
Table 8: Tripping characteristic lag time TGD ELM-12
Switch off
time
in ms
Warning
limit default
Current (I)
in A
4A Range
Current (I)
in A
6A Range
Current (I)
in A
8A Range
Current (I)
in A
10A Range
Current (I)
in A
12A Range
n.a.
Prewarning
(Alarm1):
default value
I > 3.20A
I > 4.80A
I > 6.40A
I > 8.00A
I > 9.60A
Alarm
(Alarm2):
default value
I > 4.00A
I > 6.00A
I > 8.00A
I > 10.00A
I > 12.00A
t = ∞
n.a.
I < 4.40A
I < 6.60A
I < 8.80A
I < 11.00A
I < 13.20A
t = 5000
I < 5.00A
I < 7.40A
I < 9.50A
I < 14.00A
I < 18.00A
t = 1000
I < 6.00A
I < 9.00A
I < 14.00A
I < 18.00A
I < 20.00A
t = 100
I < 10.00A
I < 14.00A
I < 18.00A
I < 20.00A
I < 24.00A
t = 30
I < 18.00A
I < 18.00A
I < 28.00A
I < 30.00A
I < 34.00A
t = 10
I < 20.00A
I < 20.00A
I < 44.00A
I < 48.00A
I < 48.00A
t = 5
I > 20.00A
I > 20.00A
I > 44.00A
I > 48.00A
I > 48.00A
5.1.1 Alarm and Prewarning Configuration
The Alarm and Prewarning level can be configured in range of 5..105% with a step width of 1mA.
5.1.2 Take over and readability of configuration
Any parameterization of characteristic, tripping current limit or other parameter can be read back immediately
after write process, but changes will not be active. The TGD ELM device will continue to operate according
the prior settings.
To take over the latest configuration it is necessary to either perform a power cycle, execute the reset device
command or by switching the output off and on again through the push button.
5.1.3 Specified range for current measurement and failure
TGD ELM-6: 0.50A … 24.00A; failure: < 400mA
TGD ELM-12: 2.00A … 50.00A; failure: < 1,5A