User Documentation

Title: topGUARD IO-Link Register Description
2020.02.17, Page 20/21
released
Table 6: Tripping characteristic lag TGD ELM-6
Switch off
time
in ms
Warning
limit de-
fault
Current (I)
in A
1A Range
Current (I)
in A
2A Range
Current (I)
in A
3A Range
Current (I)
in A
4A Range
Current (I)
in A
5A Range
Current
(I) in A
6A Range
n.a.
Prewarn-
ing
(Alarm1):
default
value
I > 0.80A
I > 1.60A
I > 2.40A
I > 3.20A
n.a.
I > 4.80A
Alarm
(Alarm2):
default
value
I > 1.00A
I > 2.00A
I > 3.00A
I > 4.00A
n.a.
I > 6.00A
t = ∞
n.a.
I < 1.10A
I < 2.20A
I < 3.30A
I < 4.40A
n.a.
I < 6.60A
t = 5000
I < 2.00A
I < 3.00A
I < 4.00A
I < 5.00A
n.a.
I < 7.40A
t = 1000
I < 3.00A
I < 4.40A
I < 5.00A
I < 6.00A
n.a.
I < 9.00A
t = 100
I < 6.00A
I < 8.00A
I < 9.00A
I < 10.00A
n.a.
I < 14.00A
t = 30
I < 12.00A
I < 13.00A
I < 15.00A
I < 18.00A
n.a.
I < 18.00A
t = 10
I < 15.00A
I < 15.00A
I < 18.00A
I < 20.00A
n.a.
I < 20.00A
t = 5
I > 15.00A
I > 15.00A
I > 18.00A
I > 20.00A
n.a.
I > 20.00A
Table 7: Tripping characteristic medium time TGD ELM-12
Switch off
time
in ms
Warning
limit default
Current (I)
in A
4A Range
Current (I)
in A
6A Range
Current (I)
in A
8A Range
Current (I)
in A
10A Range
Current (I)
in A
12A Range
n.a.
Prewarning
(Alarm1):
default value
I > 3.20A
I > 4.80A
I > 6.40A
I > 8.00A
I > 9.60A
Alarm
(Alarm2):
default value
I > 4.00A
I > 6.00A
I > 8.00A
I > 10.00A
I > 12.00A
t = ∞
n.a.
I < 4.40A
I < 6.60A
I < 8.80A
I < 11.00A
I < 13.20A
t = 5000
I < 5.00A
I < 7.40A
I < 9.50A
I < 14.00A
I < 18.00A
t = 1000
I < 6.00A
I < 9.00A
I < 14.00A
I < 18.00A
I < 20.00A
t = 100
I < 10.00A
I < 14.00A
I < 19.00A
I < 20.00A
I < 22.00A
t = 10
I < 18.00A
I < 18.00A
I < 40.00A
I < 40.00A
I < 40.00A
t = 5
I > 18.00A
I > 18.00A
I > 40.00A
I > 40.00A
I > 40.00A