User Documentation
Title: topGUARD IO-Link Register Description
2020.02.17, Page 17/21
DocVersion:
1.2
released
4.3.3 Event Codes for topGuard IO-LINK
In some engineering tools the event codes are prefixed with 0xFFFF.
Table 4 Events Codes for top Guard IO-LINK
Event Name
Event Code
Event Type
Event Mode
Length [Bits]
Comment/ Description
TGD-ELM <N> - Over Voltage Peak
6144
+
N-1
Information
Singleshot
1 bit
Signals an Over Voltage Peak
at the corresponding ELM de-
vice.
Condition:
U
In
>32V for t>200ms
TGD-ELM <N> - Under Voltage Peak
6208
+
N-1
Information
Singleshot
1 bit
Signals an Under Voltage Peak
at the corresponding ELM de-
vice.
Condition:
U
In
<17.5V for t>200ms
TGD-ELM <N> - Device Temperature
>100°C
6272
+
N-1
Warning
Appears / Dis-
appears
1 bit
Signals, that temperature on
corresponding ELM device ex-
ceeds 100°C.
Condition:
T > 100°C
TGD-ELM <N> - Reverse Voltage
Output
6336
+
N-1
Information
Singleshot
1 bit
Signals an Reverse Voltage
Peak at the corresponding ELM
device.
Condition:
U
Out
>5V for t>2s, when DC Out-
put is disabled
TGD-ELM <N> - Off
36000
+
N-1
Information
Singleshot
1 bit
Signals, that the TGD-ELM
State of the corresponding ELM
device is switched to " device
off".
Condition:
Switch to state “device on” via
push button or after start up re-
garding to the "TGD-ELM State
Select" configuration.
TGD-ELM <N> - On
36064
+
N-1
Information
Singleshot
1 bit
Signals, that the TGD-ELM
State of the corresponding ELM
device is switched to " device
on"
Switch to state “device off” via
push button or after start up re-
garding to the "TGD-ELM State
Select" configuration.
FIM - Device Failure
36320
Error
Appears / Dis-
appears
1 bit
Signals an internal failure of the
FIM device.
CIOL - Device Temperature >60°C
36321
Information
Singleshot
1 bit
Signals, that temperature on
CIOL device exceeds 60°C.
Condition:
T > 60°C