User Documentation

Title: topGUARD IO-Link Register Description
2020.02.17, Page 16/21
released
4.3.2 System Commands for topGuard IO-LINK
Table 3: System Commands for top Guard IO-LINK
Command Name
Command
Number
Comment/ Description
Combi Restart Command
160
After the CIOL device gets the com-
mand it executes a soft restart the fol-
lowing steps are executed.
(1) Soft restart of all TGD-
ELMs
(2) Soft restart of the FIM
(3) Soft restart of the CIOL
FIM Restart Command
161
After the FIM device gets the com-
mand it executes a soft restart.
FIM Set Factory Default Command
164
After the FIM device gets the command
it configures its parameters to the de-
fined default values.
CIOL Restart Command
167
After the CIOL device gets the com-
mand it executes a soft restart.
CIOL Set Factory Default Command
168
After the CIOL device gets the command
it configures its parameters to the de-
fined default values.