User Documentation

Title: topGUARD IO-Link Register Description
2020.02.17, Page 12/21
released
Table 2 Parameters for topGuard IO-LINK
Name
Type
Length
Access
Index
Data Source/Sink
Comment/ Description
TGD-ELM Remote Off Command [<N>]
Bool
1 byte
W
332
TGD
-
ELM
Only valid at TGD-ELM State b001
(“fuse on”) or b011 (“fuse on” and
"fuse switched off after short circuit")
Otherwise it has no effect.
After the corresponding ELM device
receives the command, it sets the
state "fuse off remote". The DC output
channel will be switched off.
The "fuse switched off after short cir-
cuit" state will not be changed.
New TGD-ELM Stat: b100 (“fuse off re-
mote”) or b110 (““fuse off remote”
and "fuse switched off after short cir-
cuit").
TGD-ELM Remote On Command [<N>]
Bool
1 byte
W
333
TGD
-
ELM
Only valid at TGD-ELM State b100
(“fuse off remote”) or b110 (“fuse off
remote” and "fuse switched off after
short circuit")
Otherwise it has no effect.
After the corresponding ELM device
receives the command, it sets the
state "fuse off remote". If the state
"fuse switched off after short circuit" is
not active, the DC output channel will
be switched on, otherwise it stays off.
The "fuse switched off after short cir-
cuit" state will not be changed.
New TGD-ELM State: b001 (“fuse on”)
or b011 (““fuse on” and "fuse switched
off after short circuit").
TGD-ELM State [<N>]
3 Bit
1 byte
R
334
TGD
-
ELM
This information shows the actual fuse
state of the corresponding ELM device.
bit 0: "device on" state
bit 1: " device switched off after short
circuit state"
bit 2: " device off remote" state
If all bits are ‘0’, then the ELM device is
in statedevice off”.