User Documentation

Title: topGUARD IO-Link Register Description
2020.02.17, Page 11/21
released
Table 2 Parameters for topGuard IO-LINK
Name
Type
Length
Access
Index
Data Source/Sink
Comment/ Description
TGD-ELM Tripping Current Limit [<N>]
U16
2 bytes
R
W
328
TGD
-
ELM
Sets the “TGD-ELM Tripping Current
Limit” in mA of DC- Output of the cor-
responding ELM device.
The following tripping values can be
adjusted:
TGD ELM-6:
1000mA
2000mA
3000mA
4000mA
6000mA
Default: 6000mA
TGD ELM-12:
4000mA
6000mA
8000mA
10000mA
12000mA
Default: 6000mA
Note: The configuration of this limit
automatically sets the TGD-ELM Load
Prewarning Value to 80% and the
TGD-ELM Load Alarm Warning Value
to 100% of the configured limit. (See
5.1)
To enable the new value the corre-
sponding ELM device needs to be
restarted.
TGD-ELM restart Command [<N>]
Bool
1 byte
W
329
TGD
-
ELM
After the corresponding ELM device
gets the command it executes a soft
restart.
TGD-ELM Tripping Characteristic Curve Se-
lect [<N>]
8 Bit
1 byte
R
W
330
TGD
-
ELM
Selects the tripping characteristic of
the corresponding ELM device. The fol-
lowing values are supported:
0x01 = normal time
0x02 = lag time
To enable the new value the corre-
sponding ELM device needs to be
restarted.