User Documentation
Title: topGUARD IO-Link Register Description
2020.02.17, Page 10/21
DocVersion:
1.2
released
Table 2 Parameters for topGuard IO-LINK
Name
Type
Length
Access
Index
Data Source/Sink
Comment/ Description
TGD-ELM Load Alarm Warning Value [<N>]
U16
2 bytes
R
W
327
TGD
-
ELM
Sets the threshold of the current value
in mA for the
Load Alarm Warning state of the corre-
sponding top Guard ELM.
The value can be configured between
5% and 105% of the configured TGD-
ELM Tripping Current Limit, but must
not be below 0.5A for the TGD ELM-6
and 2.0A for the TGD ELM-12 (see 5.1).
Default value = 100% of
configured TGD-ELM Tripping Current
Limit.
To enable the new value the corre-
sponding ELM device needs to be
restarted.