Power Monitor / Power Monitor 51A Quick guide to set up a connection with the Power Monitor devices through the Weidmüller Serial/Ethernet Converter
1.1 Revision history Version Date Change 0.0 11/2013 First edition 1.0 03/2015 Page 5, software Power Monitor Manager updated from version 1.10 to version 1.20 1.2 Contact address Weidmüller Interface GmbH & Co. KG PO Box 3030 32720 Detmold Klingenbergstraße 16 32758 Detmold Germany Phone Fax E-mail Internet 1502950000/01/03.15 +49 (0) 5231 14-0 +49 (0) 5231 14-2083 info@weidmueller.com www.weidmueller.
Table of contents Table of contents 1.1 Revision history ................................................................................................................................ 3 1.2 Contact address ................................................................................................................................ 3 Table of contents ............................................................................................................... 4 2. Introduction ..................
Introduction 2. Introduction This is a quick guide to set up a connection with the Power Monitor devices through the Weidmüller Serial/Ethernet Converter. Wiring Connect the Power Monitor and the Serial/Ethernet Converter via the Modbus RTU interface. Use the connection table below. Power Monitor Serial/Ethernet Converter Pin 8 Pin 5 • Weidmüller owns the copyright of this quick guide.
Configuring Serial/Ethernet Converter 3. 6 Configuring Serial/Ethernet Converter STEP 1 Start S/E-Converter Administrator. STEP 2 Click on [Search]. If you have connected the Serial/Ethernet Converter properly to your network the software will find the device. STEP 3 Mark the device in the table. STEP 4 Click on [Configure]. 1502950000/01/03.
Configuring Serial/Ethernet Converter STEP 5 Click on [Network) to see the network configuration. Click the [Modify] check box to modify the configuration if needed. 1502950000/01/03.
Configuring Serial/Ethernet Converter 8 STEP 6 Click on the [Serial] tab. STEP 7 Click the [Modify] check box. STEP 8 Mark the device in the table. STEP 9 Click on the [Settings] button. 1502950000/01/03.
Configuring Serial/Ethernet Converter STEP 10 Set the parameters as follows: • Baud Rate: 19200 • Parity: Odd • Data Bits: 8 • Stop Bits: 1 • Flow Control: None • FIFO: Enable • Interface: RS-485, 2 wire NOTICE All values must be equal to the values in the Power Monitor. STEP 11 Confirm by clicking on [OK]. 1502950000/01/03.
Configuring Serial/Ethernet Converter STEP 12 Click the [Operating Mode] tab. STEP 13 Click the [Modify] check box. STEP 14 Mark the first row in the table. STEP 15 Click on [Settings] and set [Operating Mode] to “Real COM Mode”. STEP 16 Confirm by clicking on [OK]. 10 1502950000/01/03.
Configuring Serial/Ethernet Converter STEP 17 Click on [COM Mapping]. STEP 18 Click on [Add], check the box and confirm by clicking on [OK]. 1502950000/01/03.
Configuring Serial/Ethernet Converter 12 1502950000/01/03.
Configuring Serial/Ethernet Converter STEP 19 Click on the upper row in the main window. STEP 20 Click on [Configure]. STEP 21 Select a COM Port. 1502950000/01/03.
Configuring Serial/Ethernet Converter STEP 22 Click on the [Serial Parameters] tab. STEP 23 Set the parameters to the same values as in step 10 and on the Power Monitor, i.e. • Baud Rate: 19200 • Parity: Odd • Data Bits: 8 • Stop Bits: 1 • Flow Control: None NOTICE All values must be equal to the values in the Power Monitor. STEP 24 Confirm by clicking on [OK]. STEP 25 Click on [Apply] in the main window. 14 1502950000/01/03.
Configuring Power Monitor 4. Configuring Power Monitor Firstly, please change the protocol from MEWTOCOL to MODBUS in the Power Monitor and set communication parameters as follows: • Baud Rate: 19200 • Parity: Odd • Data Bits: 8 • Stop Bits: 1 STEP 26 Start the Weidmüller Power Monitor Manager. STEP 27 Under [Settings] select [Communication setup]. 1502950000/01/03.
Configuring Power Monitor STEP 28 Set [Network] to “RS232C“. STEP 29 Set [Communication port] to the same port as described in step 22. STEP 30 Set the other parameters to the same values as in step 10 and on the Power Monitor: 16 • Baud Rate: 19200 • Parity: Odd • Data Bits: 8 • Stop Bits: 1 1502950000/01/03.
Configuring Power Monitor NOTICE All values must be equal to the values in the Power Monitor. STEP 31 Confirm by clicking on [OK]. 1502950000/01/03.
Configuring Power Monitor STEP 32 Click on [Display]. Now there must be a connection between the Power Monitor and the computer (see status on the bottom left “Communication success”). 18 1502950000/01/03.