Approval/Certificate/Document of Conformity

KEMA
='<
(13)
SCHEDULE
(14)
to EC-Type Examination Certificate KEMA 06ATEX0177 U
Issue No. 2
Type:
PDK 2.5/4 L-PE
PDK 2.5/4 N-PE
Rated insulation voltage [V] 500
500
Rated voltage [V] 550
550
- with jumper [V] 275 275
- with skipping jumper [V] 176 176
Nominal current [A] Temperature rise 40 K 28
28
- with jumper Temperature rise 40 K
26 26
Nominal current [A] Temperature rise 45 K
30
30
- with jumper Temperature rise 45 K
27,5 27,5
Contact resistance [mO]
0,7
0,7
Rated cross section [mm
2
]
(AWG)
4(12)
4 (12)
Connectable conductor cross section
- rigid [mm
2
]
(AWG) 0,5 - 6 (20-10)
0,5 - 6 (20-10)
- flexible [mm
2
]
(AWG) 0,5 - 4 (20-12)
0,5 - 4 (20-12)
Type:
PDK 2.5/4 V
Rated insulation voltage [V]
500
Rated voltage [V]
550
- with jumper [V]
275
- with skipping jumper [V]
176
Nominal current [A] Temperature rise 40 K
29
- with jumper Temperature rise 40 K
27
Nominal current [A] Temperature rise 45 K
30,5
- with jumper Temperature rise 45 K
28,5
Contact resistance [mO]
0,7
Rated cross section [mm
2
]
(AWG)
4 (12)
Connectable conductor cross section
- rigid [mm
2
]
(AWG)
0,5 - 6 (20-10)
- flexible [mm
2
]
(AWG)
0,5 - 4 (20-12)
Protective conductor terminal blocks
Type:
PPE 2.5/4
PPE 2.5/4/3AN
Rated cross section [mm
2
]
(AWG)
4 (12)
4 (12)
Connectable conductor cross section
- rigid [mm
2
]
(AWG)
0,5-6 (20-10)
0,5-6 (20-10)
- flexible [mm
2
]
(AWG)
0,5-4 (20-12)
0,5-4 (20-12)
Type:
PPE 2.5/4/4AN
PPE 6/10
Rated cross section [mm
2
]
(AWG)
4 (12)
6 (10)
Connectable conductor cross section
- rigid [mm
2
]
(AWG)
0,5-6 (20-10)
1,5-6 (16-10)
- flexible [mm
2
]
(AWG)
0,5-4 (20-12)
1,5-10 (16-8)
Type:
PPE 6/10/3AN
PPE16
Rated cross section [mm
2
]
(AWG)
6 (10)
16 (6)
Connectable conductor cross section
- rigid [mm
2
]
(AWG)
1,5-6 (16-10)
2,5-10 (14-8)
- flexible [mm
2
]
(AWG)
1,5-10 (16-8)
2,5-16 (14-6)
CERT12 V1.1