User Documentation
22
9. Technical Data
Input 0 ... 20 mA
Input voltage max. 15 V
Operating current < 100 µA
Voltage drop 2.5 ... 3 V @ 20 mA
Input overload capacity max. 50 mA, 15 V
Output 0 ... 20 mA, max. 10 V
Load 500 Ω
Adjustment period (T99) approx. 5 ms for a load of
500 Ω
Residual ripple < 10 mV
eff
General data
Chopper frequency approx. 200 kHz
Transmission errors < 0.1 % of end value +
0.05 % of measured value
/ 100 Ω load
Temperature effect
1)
50 ppm/K from measured
value for a load of 0 Ω
Test voltage
Input / output 510 V CA, 50 Hz
CEM
2)
EMC directive
EN 61326, EN 61326/A1
Ambient temperature
Operation -25 °C ... +60 °C
Storage -40 °C ... +85 °C
The cable lengths must not exceed 30 m.
1) Medium TC in the specified operating temperature
range of -25 °C ... +60 °C.
2) Valid for 4 ... 20 mA; minor deviations are possible
during interferences.