User Documentation
User Manual Managed Switches 
34 
If you do not enable any of the managed Weidmüller Ethernet Switches to be the Ring 
Master, the Turbo Ring protocol will automatically choose the Ethernet Switch with the 
smallest MAC address range to be the Ring Master. If you accidentally enable more than 
one Ethernet Switch to be the Ring Master, these switches will auto-negotiate to 
determine which one will be the Ring Master. 
If you use the browser interface to enable the DIP switches (by un-checking the “Disable 
the Turbo Ring DIP switch” checkbox), and then flip DIP switch 4 from ON to OFF, the 
Ring Ports and Coupling Ports that were added to all VLANs will be restored to their 
previous software settings. (For details, please refer to the “Using Virtual LANs” section of 
this manual). 
3.1.9 System File Update (Firmware and Configuration) 
3.1.9.1 Update System Files by Remote TFTP 
Following saving and restoring functions are available via a remote TFTP server: 
  Upload the current configuration to remote TFTP server 
  Download the current configuration from remote TFTP server 
  Download new firmware from remote TFTP server (The information how to download new 
firmware is described in Appendix C). 
  Upload the current logging data to remote TFTP server 
TFTP Server IP/Name 
Setting 
Description 
Factory 
Default 
IP Address of 
TFTP Server 
Specifies the IP address or name of the remote 
TFTP server. Must be set up before 
downloading or uploading files. 
None 
Configuration Files Path and Name 
Setting 
Description 
Factory 