User Documentation
User Manual Managed Switches 
172 
4.3.3 Electronic Data Sheet (EDS) File 
The EDS (Electronic Data Sheet) file contains electronic descriptions of all relevant communication 
parameters and objects of an EtherNet/IP device. It is required for RSLogix 5000 to recognize 
Weidmüller switch and its CIP capability.   
The list includes the sections which are described in our EDS file.   
• [File]   
• [Device]   
• [Device Classification]   
• [Port]   
Icon should be 32 * 32 in pixel. 
4.3.4 Commissioning with RSLogix 
To install a Weidmüller switch into an RSLogix EtherNet/IP environment, you must use Rockwell 
RSLogix 5000 version 18 or later and Weidmüller managed Ethernet switches with firmware version 
3.0 or later. 
Add Weidmüller switch to the I/O configuration tree 
1.  Open RSLogix 5000 and create a new controller. Click Type and select the 
Rockwell PLC model of the PLC connected to the Weidmüller switch. Input a 
Name and Description for this new controller. 
2.  (Optional) Add an Ethernet Bridge Module to the Controller Backplane 
Configuration (e.g. 1756-EN2T Ethernet Bridge), if the selected Rockwell PLC 
does not provide an Ethernet interface. In the controller organizer window, select 
I/O Configuration, right click 1756 Backplane and select New Module. 