User Documentation
  4      5  6    V1.0 / 2020-11-02 
8.  Wiring Redundant Power Inputs 
The switch supports redundant power supply inputs. For wiring via 6-pin terminal 
connector please refer to below illustration. 
 Warning / Avertissement 
 Take into consideration the following guidelines before wiring the device 
o Tenez compte des directrices suivantes avant de câbler l’appareil. 
  Terminal block is mating with Plug and suitable for 12-24AWG. Torque 
value 4.5 lb-in. 
o Le bornier est compatible avec les connecteurs et convient pour 12-
24AWG. Valeur de couple 4,5 lb-in. 
  The temperature rating of the input connection cable should higher than 
105°C. 
o La température de service nominale du câble d’entrée doit être 
supérieure à 105 °C. 
  Supplied by SELV source evaluated by UL 61010-1 or 61010-2-201 
power supply only. 
o Fourni par la source SELV évaluée uniquement par l'alimentation UL 
61010-1 or 61010-2-201. 
9.  Communication Connections 
Switch IE-SW-EL16-14TX-2FESFP is equipped with following communication interfaces: 
14x  10/100Base-T(X) ports 
2x  100Base-FX SFP slots to be used with SFP Transceivers (mini-GBIC 
Please only use cables suitable for the respective type of communication and ensure that 
signals are protected from possible interference. 
9.1  10/100Base T(X) RJ45 Ports 
The 10/100BaseT(X) ports located on Ethernet Switch’s front panel are used to connect 
to Ethernet-enabled devices. Below we show pinouts for both MDI (NIC-type) ports and 
MDI-X (HUB/Switch-type) ports. Auto MDI-X ensures that both wiring-schemes are 
supported (Automatic crossover function). 
10/100Base T(X) RJ45 Pinouts 
MDI Port Pinouts  MDI-X Port Pinouts  8-pin RJ45 
Pin  Signal  Pin  Signal   
1  Tx+  1  Rx+ 
2  Tx-  2  Rx- 
3  Rx+  3  Tx+ 
6  Rx-  6  Tx- 
9.2  100Base-FX SFP (mini-GBIC) Fiber Port 
The  100Base-FX  type  slots,  require  100Base-FX  SFP (mini-GBIC)  fiber transceivers  to 
work properly. Weidmüller provides transceiver models for various distance requirements. 
Please only use SFP modules and cables that are compatible with each other to establish 
an optical connection. 
LC-Port with separate Transmit and Receive Port: 
Remember to connect the Tx (transmit) port of device I to the Rx (receive) port of device 
II, and the Rx (receive) port of device I to the Tx (transmit) port of device I 
LC-Port Pinouts  LC-Port to LC-Port Cable Wiring 
Note about possible loss of data packages in case of “Duplex mismatching” 
If the switch’s auto-negotiation port is connected to a non-negotiating device, 
then the switch will set its port transmission speed same as the connected 
device but is unable to correctly detect the duplex mode. 
As result the port is set to the correct speed but is using always the half duplex 
mode as required by the IEEE 802.3u standard in such cases.  
For correct transmission, the non-negotiating port must be set to half-duplex 
mode (speed can be either 10 Mbps or 100 Mbps, it always will be recognized 
automatically by an Auto-Negotiation-Device). 
10.  LED Indicators 
The front panel of the Ethernet Switch contains several LED indicators. The function of 
each LED is described in the table below. 
LED  Color  Status  Description 
PWR1  Green 
On 
Power is being supplied to power input 
PWR1. 
Off 
Power is not being supplied to power input 
PWR1. 
PWR2  Green 
On 
Power is being supplied to power input 
PWR2. 
Off 
Power is not being supplied to power input 
PWR2. 
LNK/ACT 
(RJ45 LAN 
Ports) 
Green 
On  Port link is active. 
Off  Port link is inactive. 
Blinking  Transmitting data. 
10/100M 
(RJ45 LAN 
Ports) 
Amber 
On  Port speed is 100 Mbps. 
Off  Port speed is 10 Mbps. 
100M 
(Fiber Port 15-
16) 
Green 
On  Port link is active. 
Off  Port link is inactive. 
Blinking  Transmitting data. 
11.  Specifications 
Technology 
Standards  
IEEE 802.3 for 10Base-T, 
IEEE 802.3u for 100BaseTX and 100BaseFX 
IEEE 802.3x flow control 
Processing Type  Store and Forward 
MAC Table size  4K 
Packet buffer size  2.75 Mbit 
Backplane bandwidth  3.2 Gbps 
Interfaces 
RJ45 Ports 
10/100BaseT(X) auto negotiation speed, Full/Half duplex 
mode and auto MDI/MDI-X connection 
Fiber optic Port  100BaseSFP slot 
LED Indicators 
PWR1, PWR2 (Power), LAN Port Link/Activity and Port 
speed, SFP Port Link/Activity 
Power 
Input Voltage  24 V DC (12 - 48 V DC) ,2 redundant inputs 
Input Current @24 VDC  0.34 A 
Connection  One removable 6-pin terminal block, Wiring cable 12-24AWG
Overload Current 
Protection 
Present 
Reverse Polarity 
Protection 
Present 
Physical Characteristics 
Housing  IP30 protection, metal 
Dimension (W x H x D)  74 x 170 x 140 mm (2.91 x 6.69 x 5.51 in) 
Weight   1120 g 
Installation  DIN-rail 
Environmental conditions 
Operating Temperature  -40 to 75°C (-40 to 167°F) 
Storage Temperature  -40 to 85°C (-40 to 185°F) 
Ambient Relative 
Humidity 
5 to 95% (non-condensing) 
Altitude  up to 2000 m 
Regulatory Approvals 
Safety  UL 61010-1; UL 61010-2-201 
EMC 
EN 55032, EN 55024, FCC Part 15 Subpart B Class A 
IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV,  
IEC 61000-4-3 RS: 80 MHz to 1 Ghz: 3 V/m,  
IEC 61000-4-4 EFT: Power: 0.5 kV; Signal: 0.5 kV,  
IEC 61000-4-5 Surge: Power: 0.5 kV; Signal: 1 kV,  
IEC 61000-4-6 CS: 3 Vrms 
Shock  IEC 60068-2-27 
Free Fall  IEC 60068-2-31 
Vibration  IEC 60068-2-6 
MTBF 
Time  719.800 hrs 
Database  Telcordia SR332 
Warranty 
Time Period  5 years 
Contact Information 
Weidmüller Interface GmbH & Co. KG 
Klingenbergstraße 26, 32758 Detmold / Germany 
Phone +49 (0) 5231 14-0, Fax +49 (0) 5231 14-292083 
E-Mail weidmueller@weidmueller.com, Internet www.weidmueller.com 