User Documentation

- 5 -
DIP Switch Settings
Serial Connection
SW1
SW2
RS-232
ON
OFF
RS-422
ON
ON
RS-485 4-wire
OFF
OFF
RS-485 2-wire
OFF
ON
Built-in 120 Ω
Terminator
SW3
SW4
Enable
ON
Disable
OFF
Ring mode
ON
Point to Point mode
OFF
The S1 DIP Switch is located inside the Serial/Fiber Converter. When the
Serial/Fiber Converter is in RS-485 mode, use this DIP switch to configure
RS-485 data direction control, data format, and baudrate. When the Serial/Fiber
Converter is in RS-232/422 mode, the S1 DIP switch cannot affect RS-232/422
communication.
RS-485 Data Direction Control Settings
RS-485 Data Direction Control
S1 Pin 1
Auto Baudrate (default setting)
OFF
Fixed Baudrate
ON
NOTE
DIP Switch S1 is only present at models with hardware revision
3.3.0 or later. We recommend users to use Auto Baudrate and
setting S1 Pin 1 to OFF. The default setting is OFF.
Data Format Settings
Data Format
S1 Pin 2
S1 Pin 3
S1 Pin 4
7 Bits
OFF
ON
ON
8 Bits
ON
OFF
ON
9 Bits
OFF
OFF
ON
10 Bits
ON
ON
OFF
11 Bits
OFF
ON
OFF
12 Bits
ON
OFF
OFF
Baudrate Settings
Baudrate
S1 Pin 5
S1 Pin 6
S1 Pin 7
S1 Pin 8
S1 Pin 9
50
OFF
ON
ON
ON
ON
75
ON
OFF
ON
ON
ON
110
OFF
OFF
ON
ON
ON
134.5
ON
ON
OFF
ON
ON
150
OFF
ON
OFF
ON
ON
300
ON
OFF
OFF
ON
ON
600
OFF
OFF
OFF
ON
ON
1200
ON
ON
ON
OFF
ON
1800
OFF
ON
ON
OFF
ON
2400
ON
OFF
ON
OFF
ON
4800
OFF
OFF
ON
OFF
ON
7200
ON
ON
OFF
OFF
ON
9600
OFF
ON
OFF
OFF
ON
19200
ON
OFF
OFF
OFF
ON
38400
OFF
OFF
OFF
OFF
ON
57600
ON
ON
ON
ON
OFF
115200
OFF
ON
ON
ON
OFF
230400
ON
OFF
ON
ON
OFF
460800
OFF
OFF
ON
ON
OFF
921600
ON
ON
OFF
ON
OFF