User Documentation

- 47 -
4. Click button Configuration and select tab Mode (Default tab)
-Port 2 to communicate with serial slaves behind the Modbus
Gateway with IP 192.168.1.110-Port 2 is assigned to
-Port 2. For this reason we configure the -Port 2 running in
RTU Master mode because the PC is running as Modbus RTU Master..
5. Active checkbox ProCOM Enable and select RTU Master Mode of Port 2 as shown above.
Note: -Ports 3, 4 and 5 we will ignore because we only
need ProCOM-
6. Click button OK to apply the changes.

virtual Com-Port 2.
This way, when Modbus RTU Master application sends a request to virtual Com-Port 2
(provided by ProCOM), the driver will forward the request to the enabled ProCom-Port 2 of the
Gateway. Then the Gateway forwards the request to the target Modbus device using the pre-set
Modbus device mode and Slave ID.