User Documentation

1 2
16
Energy Meter D650
Quick Guide
Supplement to operation manual
• Installation
• Communication settings
• "ecoExplorer go" software settings (see link and QR code)
3
"ecoExplorer go" software device confi guration
Basic settings
1. Right-click to open the context menu for
your device:
- In the "Projects" > "Your project“ >
"Devices" > "By device type" >
"Energy Meter D650" > "Device x" window.
Recording settings
If necessary, check and confi gure the recorded
values that the measurement device is to save in
the "Recording confi guration" menu.
A recording contains one measured value or the
mean value of the measured value.
Recommendation:
18 19 20
12 13 14
5 76
2. Click the "Confi guration" menu item in the
context menu.
3. The "Confi guration [Device x]" window is
displayed in the right half of the work area.
4. Enter your individual device name in the
„Name“ input fi eld in the "Identity" in the
"Confi guration" window.
5. Enter the voltage and current ratios in the
input fi elds in the "Transformer" menu in the
"Confi guration" window.
6. In the selection lists in the "Connection
variants" menu in the "Confi guration"
window, select the connection variants for
voltage and current measurement on your
device (see the operation manual).
In order to compare recordings of transients and
events with recordings of other measurement
points, synchronise the device time with UTC
time.
NOTE!
To avoid data loss, save your changes
to the device confi guration by pressing
"Transfer" or "Transfer to"!
7. In the "Nominal values" menu in the
"Confi guration" window, select the
nominal frequency in accordance with
the network ratios that are present. Enter
the nominal values for the phases as
a reference, in order to detect events
(overvoltage/undervoltage and over-
current).
NOTE!
This device confi guration describes the
basic settings. Additional device settings
required for various functions are provided
in the software's operating instructions
(available online).
The device only determines measured values
if measured voltage of >10 Veff is present on
at least one voltage measurement input.
Voltage measurement
m
CAUTION!
Risk of injuries or
damage to the device
Failure to observe the connection conditions
for the voltage measurement inputs can cause
injuries to you or damage to the device.
Therefore, note the following:
The voltage measurement inputs
- must not be occupied with DC voltage.
- must be provided with a suitable,
labelled fuse that is positioned close by
and a circuit breaker (alternatively:
a line safety switch).
- are dangerous to touch.
Voltages that exceed the permissible
network rated voltages must be
connected via a voltage transformer.
Measured voltages and currents must
derive from the same network.
NOTE!
As an alternative to the fuse and circuit
breaker, you can use a line safety switch.
Establish the connection to the PC
The 4 most common connections for communication
between the PC and the device are described below:
m
CAUTION!
Damage to property due to
incorrect network settings
Incorrect network settings can
cause faults in the IT network!
Obtain information from your network
administrator about the network settings
for your device.
PC
RS232
The PC and the Energy Meter D650 require a static IP address.
1.
(gedrehtes Patchkabel)
3.
Energy Meter D650
connected via an
Energy Analyser D550 as a gateway.
Energy Analyser
D550
RS485
Ethernet
RS485
PC
2.
(gedrehtes Patchkabel)
USB
RS485
PC
RS485
RS485
Energy Meter D650
connected
via interface converters.
USB
4.
(gedrehtes Patchkabel)
RS485
PC
Energy Meter
D650
RS485
RS485
Energy Meter D650
connected via interface converters.
RS232 RS232
NOTE!
For information on including your
device in your Profi bus network, see
the Operation manual.
15
Display mode
The most important settings on the device
are carried out in programming mode (PRG).
Address Content
PRG
Programming mode
After the power returns, the device is in display
mode. In display mode:
Use button 1 to select the phase for the
measured values.
Use button 2 to scroll between the measured
values for current, voltage, power, etc.
Fig. Display example for "Display mode",
measured value displayed: U
L1-N
= 230.0V.
N L1
R x D TxD
V
L1 L2 L3 L4
Input Output
When you press and hold buttons 1 and 2
simultaneously for approx. 1 second, the device
switches to programming mode as long as no
display password has been confi gured:
The text "PRG" is shown on the display.
The fi rst digit in the address fl ashes.
NOTE!
For further information
on measured value indications and
the factory settings
on parameter lists and addresses
on the display password
is provided in the operation manual.
Fig. Display example for "Programming mode",
address 000 with a content of 5,000.
NOTE!
You can make further settings in the
software.
Voltage transformer ratios can be assigned to each of
the 4 voltage transformer inputs on the device.
The factory setting is 400 V/400 V (direct measurement).
In addresses 002 and 003
program the same voltage transformer ratios for all
4 phases.
voltage transformer ratios that are entered
overwrite addresses 012 to 043.
In addresses 012 to 043
program voltage transformer ratios individually for
each phase.
The device handles programmed values in
addresses 012 to 043 with priority, whereupon it sets
addresses 002 to 003 to 0.
Addr. Voltage transformer values
002 L1 L2 L3 L4 (primary)
003 L1 L2 L3 L4 (secondary)
012 L1 (primary)
013 L1 (secondary)
022 L2 (primary)
023 L2 (secondary)
032 L3 (primary)
033 L3 (secondary)
042 L4 (primary)
043 L4 (secondary)
Parameter list excerpt of "voltage transformer values"
2 connection variants for measuring the device's
voltage:
1. Connection variant 0: Voltage measurement
- direct in 3-phase 4-conductor networks.
- via 3 voltage transformers in 3-phase 4-con-
ductor networks.
- in single-phase 3-conductor systems.
2. Connection variant 1: Voltage measurement
- direct in 3-phase 3-conductor networks.
- via 2 voltage transformers (Aron circuit) in
3-phase 3-conductor networks.
Addr. Connection var. Voltage measurement
111
0 = 3-phase 4-conductor networks
(factory setting)
1 = 3-phase 3-conductor networks
Parameter list excerpt of "voltage transformer connection
variants"
Voltage transformer ratio confi guration
NOTE!
For further information on voltage
transformer ratios, see the operation
manual.
Sample confi guration: Voltage transformer ratios
Display example 1:
The primary voltage of each voltage
transformer on the 4 voltage measurement
inputs is set to 765 V.
Display example 2:
The secondary voltage of each voltage
transformer on the 4 voltage measurement
inputs is set to 400 V.
See the "Parameter list excerpt of voltage transformer values"
table in step 14 to obtain the address for your voltage transformer
measurement input and enter the voltage transformer value as follows:
1. Switch to programming mode -
press and hold buttons 1 and 2 for 1 second.
2. The 1st position in the address area fl ashes.
3. Use button 2 to select the 1st position in the address.
4. Press button 1 to confi rm the entry.
5. The 2nd position in the address area fl ashes.
6. Use button 2 to select the 2nd position in the address.
7. Press button 1 to confi rm the entry.
8. The 3rd position in the address area fl ashes.
9. Use button 2 to select the 3rd position in the address.
10. Press button 1 to confi rm the entry.
11. The position that is to be programmed in the content area
ashes.
12. Use button 2 as described above to program the voltage
value for the address area that you set.
Note that the unit can also be set
for the primary voltages.
Handle these in accordance with this programming procedure
for each voltage transformer ratio of your voltage transformer
measurement inputs.
NOTE!
The device handles programmed values in addresses 012 to 043 with priority, whereupon it sets
addresses 002 and 003 to 0.
Set up the PC connection for the Energy Meter
D650 via the Energy Analyser D550 as gateway
1. Confi gure your Energy Analyser D550 as a
"DHCP client" via an Ethernet cable to your PC
(device IP address is assigned automatically,
see the operation manual and the device's
quick guide).
2. Connect your Energy Meter D650 to the Energy
Analyser D550 via the RS485 interface (see
step 19).
"ecoExplorer go" software
Install the software on your computer and proceed
as follows:
1. Open the software on your PC.
2. In the menu bar, select "File" >
"New project". If the project already exists,
open it by selecting "File" >
"Open project“.
3. The "New project" window is displayed.
4. In step 1, "Select project", click "Continue".
5. In step 2, "Project path", select the:
- "Project name".
- "Project path".
6. Click "Finish".
7. Your project is displayed on the left in the
"Projects" window in the work area.
"ecoExplorer go" software settings
Insert the Energy Analyser D550 into the project:
1. In the menu bar, select "File" >
"New fi le".
2. The "New fi le" window is displayed.
3. In step 1, "Select fi le type", select the "File
type" for your device in the "Measurement
devices" category (Energy Analyser D550).
4. Click "Next".
5. The "Confi gure connection"
step is displayed in the window.
6. In the "Connection type" selection list, select
"TCP/IP" and enter the IP address for your
device in the "Host" eld.
Use addresses 300 to 303 to determine the
IP address for your Energy Analyser D550 in
programming mode (see operation manual and
quick guide for the Energy Analyser D550).
7. Click
"Connection test".
8. If the connection test is positive, the "Display
device information" window with the serial
number, hardware revision and fi rmware version
is displayed.
9. Click "OK".
10. Complete the "Insert new device into the
project" step by clicking "Finish"
Integrate the Energy Meter D650 into the project:
1. In the project window, click the plus icon in
front of the "Devices" directory.
2. In the "Devices" directory, click the plus icon
in front of the "By device type" subdirectory.
3. The Energy Analyser D550 that was installed
previously is displayed.
4. Right-click the "By device type" subdirectory.
5. Select the "New" menu item in the context
menu.
6. Click the menu item for your device in the
submenu.
Display:
Example of
"Confi guration of
Energy Analyser D550
(master device)“,
device address 200,
content 001.
Display:
"Setting the Baud rate"
on the Energy Analyser
D550 and Energy Me-
ter D650 (and further
Slave devices).
NOTE!
In the RS485 bus structure assign the slave
devices (Energy Meter D650)
different device addresses compared to
each other.
different device addresses to the master
device (e.g Energy Analyser D550).
Device Addr. Setting range Standard
Energy Analyser
D550
200
1 to 255 1
Energy Meter
D650
NOTE!
Assign the same Baud rate to all devices
integrated into the RS485 bus structure
(master-slave principle).
Parameter list excerpt: Energy Analyser D550 and Energy Meter
D650 "Device addresses".
Device Addr. Setting range Standard
Energy Analyser
D550
202
1 to 5 4
Energy Meter
D650
Parameter list excerpt: Energy Analyser D550 and Energy Meter
D650 "Baud rate, RS485".
Address Content
PRG
NOTE!
For further information on parameter
lists, device addresses and Baud rates,
see the operation manual.
Display:
Example of
"Confi guration of
Energy Meter D650
(slave device)“,
device address 200,
content 002.
Address Content
PRG
Address Content
PRG
8. In the "Measurement devices" category,
select the Energy Meter D650 "File type".
9. Click "Next".
10. The "Confi gure connection"
step is displayed in the window.
11. Important settings in "Confi gure connection":
- In the selection list, select the "Ethernet
gateway (e.g. for devices on the RS485)"
connection type.
- In the "Address" input fi eld, enter the IP address
for your Energy Analyser D550 (read address
300 to 303 from the device, see step 18).
- In the "Device address" selection fi eld, select
the device address for your Energy Meter
D650 (read or set address 200 on the device,
see step 18).
12. Click
"Connection test".
13. If the connection test is positive, the "Display
device information" window with the serial
number, hardware revision and fi rmware
version is displayed.
14. Click "OK".
15. Complete the "Insert new device into the
project" step by clicking "Finish".
Energy Meter D650
The device has 2 serial interfaces:
RS232
RS485
The most common method of connecting the
Energy Meter D650 to a PC is via the RS485
interface, using an Energy Analyser D550
as a gateway.
A
B
A
B
RS485 bus
e.g. connection to the
Energy Analyser D550
as a gateway (master)
e.g. connec-
tion of further
slave devices
Correct
Incorrect
Terminal strip (switching cabinet).
Device with RS485 interface
(without termination resistor).
Device with RS485 interface
(termination resistor on the device).
Example: PC connection via RS485 interface and Energy Analyser D550 as gateway
NOTE!
In order to include the Energy Meter D650
in an RS485 bus structure (master-slave
principle) with the Energy Analyser D550
as a master device, for address 203
in the Energy Analyser D550, enter a 1
(Modbus RTU/master)!
in the Energy Meter D650, enter a 0
(Modbus RTU/slave)!
A B
RS485 bus structure
In an RS485 bus structure (line), connect all
devices according to the master-slave principle.
One segment in an RS485 bus structure can
contain up to 32 participants/devices.
Terminate the cable at the start and the end of
a segment with termination resistors (120 Ω,
0.25 W). The Energy Meter D650 does not
contain a termination resistor.
With more than 32 participants, use
repeaters to connect segments.
"ecoExplorer go" software recording settings
22
4
General information
This "Quick guide" does not replace the
operation manual. Please read and understand
the operation manual enclosed with the
product fi rst.
Disclaimer
Observing the information products for
the Devices is the prerequisite for safe
operation and in order to obtain the specifi ed
performance and product features. Weidmüller
Interface GmbH & Co. KG will not be held
liable for personal injury, damage to property
or fi nancial losses due to not observing
the information products. Ensure that
your information products are legible and
accessible.
Further documentation is available on our
website at www.weidmueller.de.
Copyright notice
© 2016 - Weidmüller Interface GmbH & Co.
KG - Detmold. All rights reserved. Duplication,
editing, dissemination and other utilisation,
even in part, is prohibited.
Subject to technical changes
Please note that this document is not always
updated at the same time as further technical
developments are made to our devices.
Information and specifi cations may change.
Please obtain information on the current
version from www.weidmueller.de.
Disposal
Observe the national regulations! If necessary,
dispose of individual parts according to their
properties and existing country-specifi c
regulations, e.g. as:
Electronic waste
Plastics
Metals
or commission a certifi ed
disposal company with scrapping.
Relevant laws,
applied standards and directives
For information on the laws, standards and
directives that Weidmüller Interface GmbH & Co.
KG applied fi r the device, see the declaration of
conformity.
Safety
Safety information
The "Quick guide" is not a complete directory
of all safety measured required to operate the
device.
Special operating conditions may require
further measures. The "Quick guide" contains
instructions that must be observed to ensure
your personal safety and to prevent damage to
property.
Symbols used:
c
This symbol is an addition to the
safety instructions and indicates
an electrical hazard.
m
This symbol is an addition to the
safety instructions and indicates
a potential hazard.
This symbol with the word NOTE!
describes:
Procedures that do not pose
any risks of injures.
Important information,
procedures or handling steps.
Safety information is highlighted by a warning
triangle and are indicated as follows depending
on the degree of danger:
m
DANGER!
Indicates an imminent danger that
causes severe or fatal injuries.
m
WARNING!
Indicates a potentially hazardous
situation that can cause severe
injuries or death.
m
CAUTION!
Indicates a potentially hazardous
situation that can cause minor
injuries or damage to property.
Safety measures
When operating electrical devices, certain parts
of these devices are invariably subjected to
hazardous voltage. Therefore, severe bodily
injuries or damage to property can occur if they
are not handled properly:
Before connecting connections, earth the
device at the ground wire connection if present.
Hazardous voltages may be present in all
switching parts that are connected to the
power supply.
Hazardous voltages may also be present
in the device even after disconnecting the
supply voltage (capacitor storage).
Do not operate equipment with current
transformer circuits while open.
Do not exceed the threshold values specifi ed
in the operation manual; also adhere to this
when inspecting and commissioning.
Observe the safety and warning instructions in
the documents that belong to the device!
Qualifi ed staff
In order to prevent personal injuries and damage
to property, only qualifi ed staff with electrical
training may work on the device, with knowledge
of
the national accident prevention regulations
the safety engineering standards
installing, commissioning and operating the
device.
Proper use
The device is
intended to be installed in switching cabinets
and small installation distributors (see step 3,
"Assembly").
not intended to be installed in vehicles! Using
the device in non-stationary equipment is
considered an extraordinary environmental
condition and is only permitted with a special
agreement.
not intended to be installed in environments
with harmful oils, acids, gases, vapours,
dusts, radiation, etc.
The prerequisites for faultless, safe operation
of the device are proper transport and proper
storage, set-up and installation, as well as
operation and maintenance.
The device is a fast and capable network
analyser with a 500 MHz digital signal processor
(DSP) for top-hat rail installation, which:
measures and calculates electrical variables
such as voltage, current, power, energy,
harmonics, etc. in building installations, on
distribution units, circuit breakers and busbar
trunking systems.
displays measurement results and transmits
them via interfaces.
Device short description
The device is installed in switching cabinets or
in small installation distributors in accordance
with DIN 43880 on a 35 mm mounting rail
(DIN EN 60715).
The device meets the operational conditions
in accordance with DIN IEC 60721-3-3 and
is intended for weather-protected, stationary
use.
It can be mounted in any position.
Forced ventilation is not required.
Fig. Device on mounting rail in
accordance with DIN EN 60715.
Assembly Connecting the supply voltage
c
WARNING!
Risk of injury due
to electric voltage!
Severe bodily injuries of death can occur due to:
Touching bare or stripped wires that are live.
Device inputs that are dangerous to touch.
De-energise your device before starting
work! Check that it is de-energised.
The supply voltage level for the device is specifi ed
on the rating plate.
After connecting the supply voltage, an indication
is shown on the display. If no display appears,
check whether the supply voltage is within the
rated voltage range.
Fig. Connecting supply voltage
NOTE!
For further information on device functions, data and assembly, see the operation manual.
m
CAUTION!
Damage to property due
to not observing the
connection conditions or
impermissible overvoltages
Failure to observe the connection conditions
or exceeding the permissible voltage range
can damage or destroy your device.
Before connecting the device to the supply
voltage, note the following:
The voltage and frequency must meet
the specifi cations on the rating plate!
Adhere to the threshold values as
described in the operation manual!
When installing in a building, protect
the supply voltage with a UL-listed line
safety switches/a fuse (6 A, char. B)!
The circuit breaker
- must be easily accessible for the user
and be installed close to the device.
- must be labelled for the relevant
device.
Do not connect the supply voltage to the
voltage transformers.
Provide a fuse for the neutral conductor
if the source's neutral conductor
connection is not earthed.
Network systems
Network systems and maximum rated voltages (DIN EN 61010-1/A1):
Three-phase four-conductor systems
with earthed neutral conductor
Three-phase four-conductor systems
with non-earthed neutral conductor
(IT networks)
Three-phase three-conductor systems
not earthed
Three-phase three-conductor systems
with earthed phase
L1
L2
L3
EE
N
E
L1
L2
L3
E
N
R
L1
L2
L3
EE
L1
L2
EE
L
N
EE
L1
L2
L3
EE
L1
L2
N
EE
L1
L2
L3
EE
N
E
L1
L2
L3
E
N
R
L1
L2
L3
EE
L1
L2
EE
L
N
EE
L1
L2
L3
EE
L1
L2
N
EE
L1
L2
L3
EE
N
E
L1
L2
L3
E
N
R
L1
L2
L3
EE
L1
L2
EE
L
N
EE
L1
L2
L3
EE
L1
L2
N
EE
L1
L2
L3
EE
N
E
L1
L2
L3
E
N
R
L1
L2
L3
EE
L1
L2
EE
L
N
EE
L1
L2
L3
EE
L1
L2
N
EE
U
L-N
/ U
L-L
277 VLN / 480 VLL
U
L-N
/ U
L-L
277 VLN / 480 VLL
U
L-L
480 VLL
U
L-L
240 VLL
Dual-phase two-conductor systems
not earthed
Single-phase two-conductor systems
with earthed neutral conductor
Separated single-phase
three-conductor system
with earthed neutral conductor
The device can be used in
2-, 3- and 4-conductor
networks (TN, TT and
IT networks)
Domestic and
industrial settings
.
L1
L2
L3
EE
N
E
L1
L2
L3
E
N
R
L1
L2
L3
EE
L1
L2
EE
L
N
EE
L1
L2
L3
EE
L1
L2
N
EE
L1
L2
L3
EE
N
E
L1
L2
L3
E
N
R
L1
L2
L3
EE
L1
L2
EE
L
N
EE
L1
L2
L3
EE
L1
L2
N
EE
L1
L2
L3
EE
N
E
L1
L2
L3
E
N
R
L1
L2
L3
EE
L1
L2
EE
L
N
EE
L1
L2
L3
EE
L1
L2
N
EE
U
L-L
230 VLL
U
L-N
230 VLN
U
L-N
/ U
L-L
240 VLN / 480 VLL
Voltage measurement connection variants
Three-phase four-conductor system
Single-phase three-conductor system
Addr. 111 = 0, default setting (see step 14)
Three-phase four-conductor
system without voltage transformer.
Three-phase four-conductor
system with voltage transformer.
Three-phase three-conductor system
Addr. 111 = 1 (see step 14)
Three-phase three-conductor
system without voltage transformer.
Three-phase three-conductor
system with voltage transformer.
Voltage measurement L1, L2, L3 (baseline measurement)
Three-phase four-conductor
system
Single-phase three-conductor
system
L3
L2
L1
I4
S1 S2
3w 1m
L4N
Three-phase four-conductor
system with symmetrical loading
(current measurement in L1).
Three-phase three-conductor
system with symmetrical loading
(current measurement in L1).
N
L3
L2
L1
I4
S1 S2
4w 1m
L4N
Voltage measurement N/PE
Voltage measurement N/PE (current
measurement in the neutral conductor).
N
PE
I4
S1 S2
2w 1n
L4N
Voltage measurement L4
(supporting measurement)
requires voltage on the
Baseline measurement
to transmit the frequency.
9
Current measurement
The device
is only approved for measuring current with
a current transformer.
is intended for connecting current
transformers with secondary currents of
../1 A and ../5 A.
has the current transformer ratio 5/5 A set as
standard.
c
WARNING!
Risk of injury due
to electric voltage!
Severe bodily injuries of death can
occur due to:
Touching bare or stripped wires that are live.
Current measurement inputs that are dan-
gerous to touch on the device and on the
current transformers.
De-energise your device before starting
work! Check that it is de-energised.
Earth the system. To do this, use the earth
connection points with the earthing symbol.
Also earth the secondary windings on the
current transformer and all metal parts on
the transformer that are able to be touched.
"Current measurement in three-phase four-
conductor system" and additional current
measurements in the neutral conductor
(addr. 110 = 0, default setting).
Load
S
1
L3
L1
L2
S
2
N
S
1
S
2
S
1
S
2
S
1
S
2
c
WARNING!
Risk of injury due to
large currents and high
electric voltages!
Current transformers that are operated open in the
secondary side (high voltage peaks) can cause
severe bodily injuries or death.
Avoid operating current transformers when open,
short circuit transformers that are unloaded!
The device is operated using buttons 1 and
2. The service button is designated for use by
trained service employees only.
The device differentiates between display and
programming mode (see step 13).
Button intervals:
Press the appropriate button for a short time:
Scroll forwards.
Digit/value +1.
Press the appropriate button for a long time:
Scroll backwards.
Digit/value -1.
To switch between display mode and
programming mode, press and hold both
buttons simultaneously for 1 second.
The device switches from programming mode
to display mode if
no buttons are pressed for 60 seconds.
buttons 1 and 2 are pressed simultaneously
for 1 second.
Operation and button functions
Button 1 and button 2
Supply voltage
Temperature
measurement input
4 x current measurement 4 x voltage measurement
RS232 RS485
2 digital inputs
2 digital outputs
A B
Service button Display
NOTE!
For further information on button
functions and parameter settings, see
the operation manual.
NOTE!
Changes are only applied after exiting
programming mode.
Current transformer ratio confi guration
Current transformer ratios can be assigned to each
of the 4 current transformer inputs on the device.
The factory setting is 5 A/5 A.
In addresses 000 and 001
program the same current transformer ratios for
all 4 phases.
current transformer ratios that are entered
overwrite addresses 010 to 041.
In addresses 010 to 041
program current transformer ratios individually
for each phase.
The device handles programmed values in
addresses 010 to 041 with priority, whereupon it
sets addresses 000 and 001 to 0.
Addr. Current transformer values
000 L1 L2 L3 L4 (primary)
001 L1 L2 L3 L4 (secondary)
010 L1 (primary)
011 L1 (secondary)
020 L2 (primary)
021 L2 (secondary)
030 L3 (primary)
031 L3 (secondary)
040 L4 (primary)
041 L4 (secondary)
Parameter list excerpt of "current transformer values"
2 connection variants for measuring the de-
vice's current:
Connection variant 0: Current measurement
via 3 current transformers in 3-phase 4-con-
ductor networks.
via 2 current transformers in networks with the
same loading.
in single-phase 3-conductor systems.
Connection variant 1: Current measurement
- via 2 current transformers (Aron circuit) in
3-phase 3-conductor networks.
Addr.
Current measurement connection variant
110
0 = 3 current transformers and
accompanying variants
(factory setting)
1 = 2 current transformers
(Aron circuit)
NOTE!
For further information on current
transformer ratios, see the operation
manual.
Parameter list excerpt of "current transformer connection variants"
17
Sample confi guration: Current transformer ratios
Display example 1:
The primary current of each current transform-
er on the 4 current measurement inputs (L1,
L2, L3, L4) is set to 64 A.
Address Content
PRG
See the "Parameter list excerpt of current transformer
values" table in step 16 to obtain the address for your
current transformer measurement input and enter the current
transformer value as follows:
1. Switch to programming mode -
press and hold buttons 1 and 2 for 1 second.
2. The 1st position in the address area fl ashes.
3. Use button 2 to select the 1st position in the address.
4. Press button 1 to confi rm the entry.
5. The 2nd position in the address area fl ashes.
6. Use button 2 to select the 2nd position in the address.
7. Press button 1 to confi rm the entry.
8. The 3rd position in the address area fl ashes.
9. Use button 2 to select the 3rd position in the address.
10. Press button 1 to confi rm the entry.
11. The position that is to be programmed in the content area
ashes.
12. Use button 2 as described above to program the current
value for the address area that you set.
Note that the unit can also be set for the primary currents.
Handle these in accordance with this programming procedure
for each current transformer ratio of your current transformer
measurement inputs.
Display example 2:
The secondary current of each current
transformer on the 4 current measurement
inputs (L1, L2, L3, L4) is set to 1 A.
Address Content
PRG
NOTE!
The device handles programmed values in addresses 010 to 041 with priority, whereupon it sets
addresses 000 and 001 to 0.
NOTE!
For further information on the current
transformer and current transformer
data, see the operation manual.
Current measurement connection variants
Addr. 110 = 0, default setting (see step 16)
1 2 3 4 5 6 7 8
I1
1 2 3 4 5 6 7 8
I2 I3 I4
I1
1 2 3 4 5 6 7 8
I2 I3 I4
I1
1 2 3 4 5 6 7 8
I2 I3 I4
I1 I2 I3 I4
1 2 3 4 5 6 7 8
I1
1 2 3 4 5 6 7 8
I2 I3 I4
I1
1 2 3 4 5 6 7 8
I2 I3 I4
I1
1 2 3 4 5 6 7 8
I2 I3 I4
I1 I2 I3 I4
Current measurement via 3 current
transformers in the three-phase
four-conductor system.
Current measurement via 2
current transformers in systems
with the same loading.
Current measurement in single-
phase three-conductor systems.
1 2 3 4 5 6 7 8
I1
1 2 3 4 5 6 7 8
I2 I3 I4
I1
1 2 3 4 5 6 7 8
I2 I3 I4
I1
1 2 3 4 5 6 7 8
I2 I3 I4
I1 I2 I3 I4
Addr. 110 = 1 (see step 16)
Current measurement via
2 current transformers (Aron
circuit) in the three-phase three-
conductor system.
1 2 3 4 5 6 7 8
I1
1 2 3 4 5 6 7 8
I2 I3 I4
I1
1 2 3 4 5 6 7 8
I2 I3 I4
I1
1 2 3 4 5 6 7 8
I2 I3 I4
I1 I2 I3 I4
Current measurement I1, I2, I3
NOTE!
There is no connection variant
for current measurement at l4; you do
not have to confi gure an address!
11
The most important technical data
Supply voltage
Protection of the
supply voltage
(fuse)
6 A, char. B
(approved i.a.w. UL/IEC)
Installation
overvoltage category
300 V CAT II
Nominal range
95 V - 240 V (45 to 65 Hz)
or DC 135 V - 340 V
Operating range +-10% of nominal range
Power
consumption
Max.
9 VA / 3.2 W
Voltage measurement
3-phase 4-conductor sys-
tems with rated voltages
(L-N/L-L)
Max. 277 V/480 V
3-phase 3-conductor sys-
tems, not earthed (L-L)
with rated voltages
Max. 480 V
Overvoltage category 300 V CAT III
Measurement voltage surge 4 kV
Protection
of voltage measurement
1-10 A
Metering range L-N
1)
0 to 600 Vrms
Metering range L-L
1)
0 to 1000 Vrms
Resolution 0.01 V
Crest factor 2 (based on 480 Vrms)
Impedance 4 MOhm / phase
Current measurement
Rated current 5 A
Rated current 6 A
Protection of current
measurement when
measuring directly (with-
out a current transformer)
6 A, char. B
(approved i.a.w. UL/IEC)
Resolution on the display 10 mA
Metering range 0.001 to 8.5 Amps
Crest factor 2 (based on 6 Amps)
Overvoltage category 300 V CAT III
Measurement voltage surge 4 kV
Power consumption approx. 0.2 VA (Ri = 5 MOhm)
Overload for 1 sec. 100 A (sinusoidal)
Sampling rate 20 kHz
NOTE!
For further technical data, see the de-
vice's operation manual.
Voltage measurement
Power consumption approx. 0.1 VA
Sampling rate 20 kHz / phase
Frequency range of the
mains frequency
45 Hz to 65 Hz
1) ... The Energy Meter D650 only measures if an L-N voltage of
>10 Veff or an L-L voltage of >18 Veff is applied to at least one
voltage measurement input.
21
Voltage measurement connection variants L4 (supporting measurement)
8 10
Address
Content
PRG
Address Content
PRG
NOTE!
For further information on supporting
measurement, see the operation manual.
The voltage measurement inputs are designed for
measurements in low voltage networks, in which
rated voltages of up to
277 V phase to earth and 480 V phase to phase
in the 4-conductor system or
480 V phase to phase in the 3-conductor system
occur.
The measurement and surge voltages meet
overvoltage category 300 V CATIII.
RECOMMENDATION!
Connect the protective earth (PE) to
measurement input V4 (L4) for a PE/N
measurement. Do not use a green and
yellow wire for this as the phase does
not have a protective function (see fi g.
"Connection variant in three-phase
four-conductor system" in step 6).
Circuit breaker
L3
N
L1
L2
Fuse (UL listed)
Load
PE
Fuse
Circuit breaker
"Voltage measurement in three-phase four-
conductor system", without voltage transformer
(addr. 111 = 0, default setting)
.
Energy Meter D650
www.weidmueller.com
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
+49 5231 14-0
+49 5231 14-292083
info@weidmueller.de
http://wmqr.eu/242549
Energy Meter
D650
Energy Meter
D650
Energy Meter
D650
Energy Meter
D650
Energy Meter
D650
Energy Meter
D650
7. The "New fi le" window is displayed.
2425840000/00/01.16
Deutsche Version:
siehe Vorderseite