User Documentation

1
2 3
8
16
17
12 14
5 6 7
11
109
4
15
2
2
N
L
Suitable network systems and maximum rated voltages (DIN EN 61010-1/A1):
L2 L3 NL1
13
Deutsche Version:
siehe Vorderseite
Safety Brief description of device Assembly
The device is a multi-functional network
analyser, which:
Measure and calculate electrical variables
such as voltage, current, frequency,
power, energy, harmonics (up to the 40th
harmonic), etc. in building installations,
on distribution units, circuit breakers and
busbar trunking systems.
Display and save measurement results
and transmit them via interfaces.
NOTE!
For further information on device functions, data and assembly, see the operation manual.
Install the device in the weatherproof front panel of
switch cabinets.
Cut-out size:
92
+0.8
x 92
+0.8
mm
Ensure!
Adequate ventilation
install the device vertically!
adhere to clearances from
neighbouring components!
Fig. Installation situation,
rear view
Connecting the supply voltage
The supply voltage level for your device is specifi ed
on the rating plate.
After connecting the supply voltage, an indication
is shown on the display. If no indication appears,
check whether the supply voltage is within the
rated voltage range
Fuse
Circuit breaker
Three-phase, four-conductor systems
with earthed neutral conductor
Three-phase, four-conductor systems
with non-earthed neutral conductor
(IT networks)
Three-phase, three-conductor systems
Non-earthed
Three-phase, three-conductor systems
With earthed phase
L1
L2
L3
EE
N
E
L1
L2
L3
E
N
R
L1
L2
L3
EE
L1
L2
EE
L
N
EE
L1
L2
L3
EE
L1
L2
N
EE
L1
L2
L3
EE
N
E
L1
L2
L3
E
N
R
L1
L2
L3
EE
L1
L2
EE
L
N
EE
L1
L2
L3
EE
L1
L2
N
EE
L1
L2
L3
EE
N
E
L1
L2
L3
E
N
R
L1
L2
L3
EE
L1
L2
EE
L
N
EE
L1
L2
L3
EE
L1
L2
N
EE
L1
L2
L3
EE
N
E
L1
L2
L3
E
N
R
L1
L2
L3
EE
L1
L2
EE
L
N
EE
L1
L2
L3
EE
L1
L2
N
EE
U
L-N
/ U
L-L
277 VLN / 480 VLL
U
L-N
/ U
L-L
277 VLN / 480 VLL
U
L-L
480 VLL
U
L-L
240 VLL
Single-phase, two-conductor systems
with earthed neutral conductor
Separated single-phase,
three-conductor system
with earthed neutral conductor
The devices can be used
in
2, 3 and 4 conductor
networks (TN, TT and
IT networks)
in residential and
industrial applications.
L1
L2
L3
EE
N
E
L1
L2
L3
E
N
R
L1
L2
L3
EE
L1
L2
EE
L
N
EE
L1
L2
L3
EE
L1
L2
N
EE
L1
L2
L3
EE
N
E
L1
L2
L3
E
N
R
L1
L2
L3
EE
L1
L2
EE
L
N
EE
L1
L2
L3
EE
L1
L2
N
EE
U
L-N
230 VLN
U
L-N
/ U
L-L
240 VLN / 480 VLL
Mains systems Voltage measurement
m
CAUTION!
Danger of injury or damage to
the device
Disregard of the connection conditions for the
voltage measurement inputs can result in injuries
or to the device being damaged.
For this reason, note that:
The voltage measurement inputs
- are not connected to DC voltage.
- are equipped with a suitable, labelled
fuse and isolation device located in
the vicinity (alternative: circuit breaker)
located nearby.
- are dangerous to touch.
Voltages that exceed the allowed network
rated voltages must be connected via
a voltage transformer.
Measured voltages and measured currents
must derive from the same network!
L2
L3
N
L1
Circuit breaker
NOTE!
If the metering range is exceeded, the
measurement device display shows
"EEE". For further information, see the
operation manual.
Connection variant 3p 4w Voltage measurement
(Addr. 509 = 0, standard setting)
Connection variants for voltage measurement
1p 2w1
(Addr. 509 = 4)
2p 4w
(Addr. 509 = 3)
1p 2w
(Addr. 509 = 6)
3p 1w
(Addr. 509 = 7)
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
N
V1 V2 V3 VN
L1
L2
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1 V2 V3 VN
N
Measured values derived from
voltage measurement inputs V2
and V3 are taken to be 0 and are
not calculated.
System with equal loading of the
phases. The measured values of
the voltage measurement input V2
are calculated.
TN-C system with 1-phase, three-
conductor connection. Measured
values derived from voltage
measurement input V3 are taken to
be 0 and are not calculated.
3 systems with equal loading of
the phases. The measured values
of the unconnected phases (L2/
L3, L1/L3, L1/L2), of the respective
systems are calculated.
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
N
V1 V2 V3 VN
L1
L2
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1 V2 V3 VN
N
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
N
V1 V2 V3 VN
L1
L2
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1 V2 V3 VN
N
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
N
V1 V2 V3 VN
L1
L2
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1 V2 V3 VN
N
Current measurement I1, I2, I3
The device
is only approved for current measurements
with a current transformer.
is intended for the connection of current
transformers with secondary currents of
../1 A and ../5 A.
has the current transformer ratio set to 5/5 A
as standard.
c
WARNING!
Danger of injury due to
electrical voltage!
Serious bodily injury or death can result from:
Contact with bare or stripped live wires.
Current measurement inputs on the device
and on the current transformer that are
dangerous to touch.
Render the system free of voltage before
starting work! Check the system is free of
electrical energy!
Earth your system! Use the earth connection
points with earthing symbols for this!
Earth the secondary windings of current
transformers and all of the metal parts of the
transformer that could be touched!
NOTE!
If the measurement range is exceeded,
the measurement device display shows
"EEE". Further information on this can
be found in the operation manual.
c
WARNING!
Risk of injury due to
large currents and high
electric voltages!
Current transformers that are operated open in the
secondary side (high voltage peaks) can cause
severe bodily injuries or death.
Avoid operating current transformers when open,
short circuit transformers that are unloaded!
L2
L3
N
L1
Load
Connection variant 3p 4w Current measurement
(I1, I2, I3) via current transformer (Addr. 510 = 0,
standard setting).
Connection variants for current measurement I1, I2, I3
3p 2i
(Addr. 510 = 1)
3p 2i0
(Addr. 510 = 2)
3p 3w3
(Addr. 510 = 3)
3p 3w
(Addr. 510 = 4)
System with equal loading of the
phases. The measured values for
current measurement input I2 are
calculated.
The measured values for the
current measurement input I2 are
calculated.
Measurement in the 3-phase
network with unequal loading.
Measurement in the 3-phase
network with equal loading.
The measured values for current
measurement inputs I2 and I3 are
calculated.
2p 4w
(Addr. 510 = 5)
1p 2i
(Addr. 510 = 6)
1p 2w
(Addr. 510 = 7)
3p 1w
(Addr. 510 = 8)
System with equal loading of the
phases. The measured values for
current measurement input I2 are
calculated.
Measured values derived from
current measurement input I3
are taken to be 0 and are not
calculated.
Measured values derived from
current measurement inputs I2 and
I3 are taken to be 0 and are not
calculated.
3 systems with equal loading of
the phases. The measured values
of the unconnected phases (L2/
L3, L1/L3, L1/L2), of the respective
systems are calculated.
L1
L2
L3
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
I1 I2 I3
L1
L2
L1
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
I1 I2 I3
L1
L2
L1
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
I1 I2 I3
L1
L2
L1
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
I1 I2 I3
L1
L2
L1
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
I1 I2 I3
L1
L2
L1
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
I1 I2 I3
L1
L2
L1
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
I1 I2 I3
L1
L2
L1
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
I1 I2 I3
L1
L2
L1
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
N
I1 I2 I3
L1
L2
L3
I1 I2 I3
L1
L2
L3
L1
L2
L3
Current measurement I4
Connection variant for current
measurement (I4) via current
transformer
Current values but not power
values can be calculated for
current measurement input I4.
Load
NOTE!
The measurement input I4 does not
require address setting on the device.
NOTE!
Further information on current data and
current transformer data can be found
in the operation manual.
The 3 most common connections for
communication between PC and device are
described in the following:
PC
USB (Typ A)
PC and device require a fi xed IP address.
1.
2.
(gedrehtes Patchkabel)
PC
RS232 RS232
RS485
Connection of the device
via interface converter.
USB (Typ B)
(gedrehtes Patchkabel)
PC
3.
Connection of the device via an
Energy Analyser D550 as gateway.
Ethernet
RS485
RS485
RS485
RS485
Establish connection to PC
More details on device confi guration and
communication can be found from section 13.
NOTE "Profi bus interface"!
Information for integrating your Energy
Meter 610-PB in your Profi bus network
can be found in the operation manual.
Recommendation for the Ethernet connection:
Use at least a CAT5 cable!
Fig. Rear of the device
m
CAUTION!
Property damage due to
incorrect network settings
Incorrect network settings can cause faults in
the IT network!
Find out the correct Ethernet network
settings for your device from your network
administrator.
The device is operated with buttons 1 and 2,
whereby the following distinctions are made:
Short press (button 1 or 2):
Next step (+1).
Longer press (button 1 or 2):
Previous step (-1).
The device differentiates between display and
programming mode.
Display mode
Buttons 1 and 2 can be used to scroll
between the measured value indications.
The measured value indication shows up to
3 measured values.
A time for the automatic display change
between the measured value indications
can be confi gured in the „ecoExplorer go“
software.
Programming mode
Hold buttons 1 and 2 depressed
simultaneously for 1 second to change
between display mode and programming
mode. The text PRG appears in the display.
Confi gure the necessary settings for the
operation of the device in programming
mode.
Controls and button functions
The programming mode can be protected with
a user password.
Button 2 switches between the programming
menus:
1. Current transformer
2. Voltage transformer
3. Parameter list
In order to switch from programming mode to display mode
press buttons 1 and 2 simultaneously for 1 second.
do not press any buttons for 60 seconds (automatic).
NOTE!
Changes are only applied after exiting
the programming mode.
NOTE!
The following section contains an
explanation of the most important
programming menus current
transformer, voltage transformer
and parameter list.
More detailed information on the
operation, display and button
functions for your device can be found
in the operation manual.
NOTE!
Changes are only applied after exiting
programming mode.
For further information on current
transformers and current transformer
ratios, see the operation manual.
Programming current transformers
1. Switch to programming mode.
2. The symbols for the programming mode
PRG and current transformer CT appear.
3. Press button 1 - the fi rst digit of the input
eld for the primary current fl ashes.
4. Use button 2 to select the value of the
1st digit.
5. Use button 1 to change to the 2nd digit.
6. Use button 2 to select the value of the
2nd digit.
7. Use button 1 to change to the 3rd digit.
8. Use button 2 to select the value of the
3rd digit.
9. Confi rm with button 1.
10. The complete number fl ashes.
11. Use button 2 to select the decimal place and
thus the unit of the primary current.
12. Confi rm with button 1.
13. The input range of the secondary current
ashes.
14. Set the secondary current (value 1 A or 5 A)
with button 2.
15. Confi rm with button 1.
16. Exit programming mode by simultaneously
pressing buttons 1 and 2 (1 sec.). Use
button 2 to change to the input fi eld for the
voltage transformer.
Programming the voltage transformer
1. Switch to programming mode.
2. The symbols for programming mode PRG,
and for the current transformer CT appear.
3. Use button 2 to change to programming
mode for the voltage transformer.
4. The symbols for Programming mode PRG,
and for the voltage transformer VT appear.
5. Press button 1 - the fi rst digit of the input
eld for the primary voltage fl ashes.
6. Use button 2 to select the value of the
1st digit.
7. Use button 1 to change to the 2nd digit.
8. Use button 2 to select the value of the
2nd digit.
9. Use button 1 to change to the 3rd digit.
10. Use button 2 to select the value of the
3rd digit.
11. Confi rm with button 1.
12. The complete number fl ashes.
13. Use button 2 to select the decimal place and
thus the unit of the primary voltage.
14. Confi rm with button 1.
15. The input range of the secondary voltage
ashes.
16. Set the secondary voltage with button 2.
17. Confi rm with button 1.
18. Exit programming mode by simultaneously
pressing buttons 1 and 2 (1 sec.). Use
button 2 to change to the programming
mode for the parameter list.
NOTE!
Changes are only applied after exiting
programming mode.
For further information on voltage
transformers and voltage transformer
ratios, see the operation manual.
Fuse (UL/IEC listed)
NOTE!
As an alternative to the fuse and circuit
breaker, you can use a line safety switch.
The voltage measurement inputs are designed for
measurements in low voltage networks, in which
rated voltages of up to
277 V phase to earth and 480 V phase to phase
in the 4-conductor system or
480 V phase to phase in the 3-conductor system
occur.
The measurement and surge voltages meet
overvoltage category 300 V CATIII.
3p 4w
(Addr. 509 = 0, standard setting)
3p 4wu
(Addr. 509 = 1)
3p 4u
(Addr. 509 = 2)
3p 2u
(Addr. 509 = 5)
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
N
V1 V2 V3 VN
L1
L2
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1 V2 V3 VN
N
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
N
V1 V2 V3 VN
L1
L2
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1 V2 V3 VN
N
Measurement with 3 phase
conductors and neutral conductor.
Measurement via voltage
transformer with 3 phase
conductors and a neutral
conductor.
Measurement with 3 phase
conductors and no neutral
conductor. Measured values which
require an N use a calculated N.
Measurement via voltage
transformer with 3 phase
conductors and no neutral
conductor. Measured values which
require an N use a calculated N.
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
N
V1 V2 V3 VN
L1
L2
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1 V2 V3 VN
N
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
L2
L3
V1 V2 V3 VN
L1
N
V1 V2 V3 VN
L1
L2
V1 V2 V3 VN
L1
L2
L3
N
V1 V2 V3 VN
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1 V2 V3 VN
N
Voltage measurement
3-phase, 4-conductor
systems with rated
voltages up to
277 V/480 V (+-10%)
3-phase, 3-conductor
systems, unearthed, with
rated voltages up to
IT 480 V (+-10%)
Overvoltage category 300 V CAT III
Measurement voltage surge 4 kV
Protection of
voltage measurement
1 - 10 A
(With IEC / UL approval)
Measurement range L-N
0
1)
to 300 Vrms
(max. overvoltage 520 Vrms )
Voltage measurement
Measurement range L-L
0
1)
to 520 Vrms
(max. overvoltage 900 Vrms )
Resolution 0.01 V
Crest factor
2.45 (related to the measurement range)
Impedance 4 MOhm / phase
Power consumption approx. 0.1 VA
Sampling rate
21.33 kHz (50 Hz), 25.6 kHz (60 Hz)
for each measurement channel
Frequency range of the
fundamental oscillation -
resolution
45 Hz to 65 Hz
0.01 Hz
1) ... The device determines measured values only if the Voltage
measurement input V1 voltage L1-N greater than 20 Vrms
(4-wire measurement) or a voltage L1-L2 of larger 34 Vrms
(3-wire measurement) is applied.
Current measurement I1 - I4
Rated current 5 A
Measurement range 0 to 6 Arms
Crest factor 1.98
Resolution 0.1 mA (display 0.01 A)
Overvoltage category 300 V CAT II
Measurement voltage
surge
2 kV
Power consumption approx. 0.2 VA (Ri = 5 mOhm)
Overload for 1 sec. 120 A (sinusoidal)
Sampling rate
21.33 kHz (50 Hz), 25.6 kHz (60 Hz)
for each measurement channel
NOTE!
Further technical data can be found in
the operation manual for the device.
Programming parameters
1. Switch to programming mode.
2. The symbols for programming mode PRG,
and for the current transformer CT appear.
3. Press button 2 twice to change to the
programming mode for the parameter list.
4. The input area of the parameter list appears.
5. Confi rm with button 1 - the fi rst digit of the
parameter address fl ashes.
NOTE!
A detailed parameter list with setting
areas and pre-settings can be found
in the operation manual or the
Modbus address list on our website.
The parameter addresses of the
device address (000) and the Baud
rate (001) are explained in the
following.
6. Use button 2 to select the value of the
1st digit.
7. Continue the process for the next digits of
the parameter address and for the parameter
settings.
8. Exit programming mode by simultaneously
pressing button 1 and 2 (1 second). Use
button 2 to change back to the input fi eld for
the current transformer.
Set the device address (parameter address 000)
In a Master-Slave network via the RS485 interface
it is possible to distinguish between a master device
and other devices with the device address.
In the case of devices within this network, for the
parameter address 000 please note
you must assign different device addresses.
the parameter setting of the parameter address
000 must lie within the range of 1 to 247
(0 and 248 to 255 are reserved).
Set the Baud rate (parameter address 001)
In a Master-Slave network via the RS485 interface,
for each device:
select a uniform Baud rate (parameter address
001) (for settings see the operation manual).
select the number of stop bits
(parameter address 003) (0=1 Bit, 1=2 Bits).
Data bits (8) and parity (none) are preset.
Technical data
General information
Net weight
(with attached connectors)
approx. 358 g
Packaging weight
(including accessories)
approx. 790 g
Battery
Lithium battery CR2032, 3 V
(approval i.a.w. UL 1642)
Service life of
background lighting
40000 h
(after this period of time
the background lighting
effi ciency will reduce by
approx. 50%)
Transport and storage
The following information applies to devices which are trans-
ported or stored in the original packaging.
Free fall 1 m
Temperature K55 (-25° C to +70° C)
Relative humidity 0 to 90% RH
Ambient coditions during operation
The device is intended for weather-protected, stationary use.
Protection class II i.a.w. IEC 60536 (VDE 0106, Part 1).
Operating temperature range K55 (-10° C .. +55° C)
Relative humidity 0 to 75% RH
Operating altitude 0 .. 2000 m above sea level
Degree of pollution 2
Mounting position vertical
Ventilation
Forced ventilation is not
required.
Protection against ingress of
solid foreign bodies and water
- Front side
- Rear side
- Front with seal
IP40 i.a.w. EN60529
IP20 i.a.w. EN60529
IP54 i.a.w. EN60529
Digital inputs
4 optional digital inputs, semiconductor relays,
not short-circuit proof.
Maximum counter frequency 20 Hz
Input signal present
18V .. 28 V DC
(typical 4 mA)
Input signal not present
0 .. 5 V DC,
current less than 0.5 mA
Digital outputs
6 digital outputs, semiconductor relays, not short-circuit proof.
Switching voltage max. 33 V AC, 60 V DC
Switching current max. 50 mAeff AC/DC
Response time 10/12 periods + 10 ms *
Pulse output (energy pulse) max. 50 Hz
* Response time e.g. at 50 Hz: 200 ms + 10 ms = 210 ms
Cable length (digital inputs and outputs)
Up to 30 m Unshielded
More than 30 m Shielded
Terminal connection capacity (power supply voltage)
Conductors to be connected.
Only one conductor can be connected per terminal!
Single core, multi-core,
ne-stranded
0.2 - 2.5 mm
2
, AWG 26-12
Terminal pins, core end sheath 0.2 - 2.5 mm
2
Tightening torque 0.4 - 0.5 Nm
Stripping length 7 mm
Terminal connection capacity (current measurement)
Conductors to be connected.
Only one conductor can be connected per terminal!
Single core, multi-core,
ne-stranded
0.2 - 2.5 mm
2
, AWG 26-12
Terminal pins, core end sheath 0.2 - 2.5 mm
2
Tightening torque 0.4 - 0.5 Nm
Stripping length 7 mm
Terminal connection capacity (voltage measurement)
Conductors to be connected.
Only one conductor can be connected per terminal!
Single core, multi-core,
ne-stranded
0.08 - 4.0 mm
2
, AWG 28-12
Terminal pins, core end sheath 0.2 - 2.5 mm
2
Tightening torque 0.4 - 0.5 Nm
Stripping length 7 mm
Terminal connection capacity (digital inputs/outputs)
Single core, multi-core,
ne-stranded
0.2 - 1.5 mm
2
, AWG 28-16
Terminal pins, core end sheath 0.2 - 1.5 mm
2
Tightening torque 0.2 - 0.25 Nm
Stripping length 7 mm
Terminal connection capacity (RS485)
Single core, multi-core,
ne-stranded
0.2 - 1.5 mm
2
, AWG 28-16
Terminal pins, core end sheath 0.2 - 1.5 mm
2
Tightening torque 0.2 - 0.25 Nm
Stripping length 7 mm
Procedure in the event of faults
Possible fault Cause Remedy
No display
External fusing for the power supply voltage has
tripped.
Replace fuse.
No current display
Measurement voltage is not connected. Connect the measuring-circuit voltage.
Measurement current is not connected. Connect measuring-circuit current.
Current displayed is too large
or too small.
Current measurement in the wrong phase. Check connection and correct if necessary.
Current transformer factor is incorrectly programmed.
Read out and program the current transformer trans-
formation ratio at the current transformer.
The current peak value at the measurement input
was exceeded by harmonic components.
Install current transformer with a larger transforma-
tion ratio.
The current at the measurement input fell short of.
Install current transformer with a suitable transfor-
mation ratio.
Voltage displayed is too large
or too small.
Measurement in the wrong phase. Check connection and correct if necessary.
Voltage transformer incorrectly programmed.
Read out and program the voltage transformer trans-
formation ratio at the voltage transformer.
Voltage displayed is too
small.
Overrange. Install voltage transformers.
The peak voltage value at the measurement input has
been exceeded by harmonic components.
Caution! Ensure the measurement inputs are not
overloaded.
"EEE" in the display See „error messages“ in the operation manual.
"EEE bAt" in the display Battery capacity is too low
Replace battery
(see "Replacing the battery" in the operation manual).
Device still does not work
despite the above measures.
Device defective.
Send the device to the manufacturer for inspection
and testing along with an accurate fault description.
www.weidmueller.com
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
+49 5231 14-0
+49 5231 14-292083
info@weidmueller.de
Energy Meter 610-PB-24
Energy Meter 610-PB-230
Installation manual
Supplement to the operation manual
Installation
Technical data
Fig. Energy Meter 610-PB-230
General
Disclaimer
The observance of the information products for
the devices is a prerequisite for safe operation
and to achieve the stipulated performance
characteristics and product characteristics.
Weidmüller Interface GmbH & Co. KG accepts
no liability for injuries to personnel, property
damage or fi nancial losses arising due to a
failure to comply with the information products.
Ensure that your information products are
accessible and legible.
Further documentation is available on our
website at www.weidmueller.de.
Copyright notice
© 2017 - Weidmüller Interface GmbH & Co.
KG - Detmold. All rights reserved. Duplication,
editing, distribution and any form of
exploitation, also as excerpts, is prohibited.
Subject to technical amendments
Make sure that your device agrees with the
installation manual.
Read and understand fi rst product-related
documents.
Keep product supporting documentation
throughout the life available and, where approp-
riate, to pass on to subsequent users.
Please inform yourself about device revisions
and the associated adjustments to the product-
related documentation on www.weidmueller.de.
Disposal
Observe the national regulations! If necessary,
dispose of individual parts according to their
properties and existing country-specifi c
regulations, e.g. as:
Electronic waste
Plastics
Metals
or commission a certifi ed disposal company with
scrapping.
Relevant laws, applied standards and directives
For information on the laws, standards and
directives that Weidmüller Interface GmbH & Co.
KG applied for the device, see the declaration of
conformity.
Safety information
The Installation manual is not a complete
directory of all safety measures required to
operate the device.
Special operating conditions may require further
measures. The Installation manual contains
instructions that must be observed to ensure
your personal safety and to prevent damage to
property.
Symbols used:
c
This symbol is an addition to the
safety instructions and indicates
an electrical hazard.
m
This symbol is an addition to the
safety instructions and indicates
a potential hazard.
This symbol with the word NOTE!
describes:
Procedures that do not pose
any risks of injures.
Important information,
procedures or handling steps.
Safety information is highlighted by a warning
triangle and is indicated as follows depending
on the degree of danger:
m
DANGER!
Indicates an imminent danger that
causes severe or fatal injuries.
m
WARNING!
Indicates a potentially hazardous
situation that can cause severe
injuries or death.
m
CAUTION!
Indicates a potentially hazardous
situation that can cause minor
injuries or damage to property.
Safety measures
When operating electrical devices, certain parts
of these devices are invariably subjected to
hazardous voltage. Therefore, severe bodily
injuries or damage to property can occur if they
are not handled properly:
Before connecting connections, ground
the device at the protective conductor
connection if present.
Hazardous voltages may be present in all
switching parts that are connected to the
power supply.
Hazardous voltages may also be present
in the device even after disconnecting the
supply voltage (capacitor storage).
Do not operate equipment with current
transformer circuits while open.
Do not exceed the threshold values specifi ed
in the operation manual and on the rating
plate. Also adhere to this when inspecting and
commissioning.
Observe the safety and warning instructions in
the documents that belong to the device!
Qualifi ed staff
The device must only be installed, put into opera-
tion and maintained by qualifi ed electricians who
are familiar with national and international laws,
provisions and standards.
Proper use
The device is
intended for installation in switch cabinets
and small installation distributors. It can be
installed in any mounting position (please
observe step 3 "Assembly").
not intended for installation in vehicles!
The use of the device in mobile equipment
is considered to be non-standard
environmental conditions and is therefore
only permitted after separate agreement.
not intended for installation in environments
with hazardous oils, acids, gases, vapours,
dusts, radiation, etc.
They should be installed in an appropriate
enclosure (such as an electrical cabinet or dis-
tributor box) which provides a suffi cient level of
protection so that live current-carry components
cannot be touched and so that dust and water
cannot penetrate the unit.
The safety of the device must not be impaired
by its installation.
The prerequisites of faultless, safe operation
of this device are proper transport and proper
storage, set-up, installation, operation and
maintenance.
All signals connected with the device’s SELV
circuit must also conform with the SELV provi-
sions.
m
CAUTION!
Damage to property due to
disregard of the installation
instructions
Failing to observe the installation instructions
can damage or destroy your device.
Ensure that there is adequate air circulation in your
installation environment; if the ambient temperatures
are high, ensure there is adequate cooling if required.
c
WARNING!
Risk of injury due
to electric voltage!
Serious bodily injury or death can result from:
Contact with bare or stripped live wires.
Device inputs that are dangerous to touch.
De-energise your device before starting
work! Check that it is de-energised.
m
CAUTION!
Damage to property due to
disregard of the connection
conditions or impermissible
voltage swells
Your device can be damaged or destroyed
by a failure to comply with the connection
conditions or by exceeding the permissible
voltage range.
Before connecting the device to the supply
voltage, please check:
Voltage and frequency correspond to the
details on the ratings plate! Threshold
values stipulated in the operation
manual have been complied with!
In building installations, the supply
voltage must be protected with a UL/IEC
approved circuit breaker / a fuse!
The circuit breaker
- must be easily accessible for the user
and be installed close to the device.
- must be labelled for the relevant device.
Do not connect the supply voltage to the
voltage transformers.
Provide a fuse for the neutral conductor
if the source's neutral conductor
connection is not earthed.
Fig. Connection example supply voltage 230 V.
The device has 3 voltage measurement inputs
and is suitable for different connection variants.
Fig. Device display
Button 1
Button 2
Delivery
Mean value
CT: Current
transformer
VT: Voltage
transformer
K1: Output 1
K2: Output 2
Password
Phase conductor-
Phase conductor
Summation
measurement
Programming
mode
Min. value NT/Delivery
Max. value, HT/Consumption
Current transformer
symbol
Unit indicator
Current transformer,
primary
Programming mode
Current transformer,
secondary
Fig. "Current transformer" input area
Unit indicator
Voltage transformer,
primary
Programming mode
Voltage transformer,
secondary
Voltage transformer
symbol
Fig. "Voltage transformer" input area
Parameter address
Programming mode
Parameter setting
Fig. "Parameter list"
input area
Serial interface
RS485 - Modbus RTU/Slave
9.6 kbps, 19.2 kbps,
38.4 kbps, 57.6 kbps,
115.2 kbps
Stripping length 7 mm
USB (receptacle)
USB 2.0, type B, max.
transfer rate 921.6 kbps
Profi bus (Energy Meter 610-PB)
- Profi bus DP/V0
- Receptacle
- 9,6kbps to 12Mbps
- D-sub, 9-pole
Energy Meter
610-PB-24/230
Energy Meter
610-PB-24/230
Energy Meter
610-PB-24/230
Energy Meter
610-PB-24/230
Energy Meter
610-PB-24/230
Energy Analyser
D550
Supply voltage
Nominal range
Option 230 V:
AC 90 V - 277 V (50/60 Hz) or
DC 90 V - 250 V, 300 V CATIII
Option 24 V:
AC 24 V - 90 V (50/60 Hz) or
DC 24 V - 90 V, 150 V CATIII
Operating range +-10% of the nominal range
Energy Meter 610-PB
Power consumption
Option 230 V: max. 7,5 VA / 4 W
Option 24 V: max. 6,5 VA / 5 W
Internal fuse,
not replaceable
Type T1A / 250 VDC / 277 VAC
according to IEC 60127
Recommended over-
current protection device
for the line protection
Option 230 V: 6-16 A
Option 24 V: 1-6 A
(Char. B)
(IEC/UL approval)
http://wmqr.eu/254086
http://wmqr.eu/254087
2576860000/00/01.18