User Documentation
2
Safety
Safety information
The "Quick guide" does not represent a full
listing of all necessary safety measures required
for safe operation of the device.
Certain operating conditions may require
further measures. The "Quick guide" contains
information that you must observe for your
own personal safety and to avoid damage to
property.
Symbols used:
c
This symbol is used as an addition
to the safety instructions and
warns of an electrical hazard.
m
This symbol is used as an addition
to the safety instructions and
warns of a potential hazard.
This symbol with the word NOTE!
describes:
• Procedures that do not entail
any danger of injury.
• Important information,
procedures or handling steps.
Safety instructions are highlighted with
a warning triangle and shown as follows,
depending on the degree of hazard:
m
DANGER!
Indicates an immediately
threatening hazard that leads to
serious or even fatal injuries.
m
WARNING!
Indicates a potentially hazardous
situation that could lead to
serious or even fatal injuries.
m
CAUTION!
Indicates a potentially hazardous
situation that could lead to minor
injuries or damage to property.
Measures for safety
When operating electrical devices certain parts
of these devices inevitable carry dangerous
voltages. This could result in serious bodily
injury or damage to property if not handled
properly:
• Before establishing electrical connections
to the device, earth it at the ground wire
connection if there is one.
• Hazardous voltages may arise in all circuit
parts that are connected to the power supply.
• Even after disconnecting the power supply,
there may still be hazardous supply voltages
present in the device (capacitor storage).
3
• Do not operate equipment with current
transformer circuits when open.
• Do not exceed the threshold values stipulated
in the operating manual - even during testing
or commissioning.
• Observe the safety and warning information in
the documents that belong to the devices!
Qualifi ed personnel
In order to avoid injuries to personnel and
property damage, only qualifi ed personnel with
electrical training are permitted to work on the
devices with knowledge
• of the national regulations for accident
prevention
• of safety standards
• of installation, commissioning and operation
of the device.
Proper use
The device is
• intended for installation in switch cabinets
and small installation distributors (please
observe step 3 "Assembly").
• not intended for installation in vehicles!
The use of the device in mobile equipment
is considered to be non-standard
environmental conditions and is therefore
only permitted after separate agreement.
• not intended for installation in environments
with hazardous oils, acids, gases, vapours,
dusts, radiation, etc.
The prerequisites of faultless, safe operation
of this device are proper transport and proper
storage, set-up, installation, operation and
maintenance.
1
General information
This "Quick guide" does not replace the
operating manual. First, please read and ensure
that you understand the operating manual that
accompanies the product.
Disclaimer
The observance of the information products for
the devices is a prerequisite for safe operation
and to achieve the stipulated performance
characteristics and product characteristics.
Weidmüller Interface GmbH & Co. KG accepts
no liability for injuries to personnel, property
damage or fi nancial losses arising due to
a failure to comply with the information
products.
Ensure that your information products are
accessible and legible.
Further documentation can be found on our
website www.weidmueller.de.
Copyright notice
© 2016 - Weidmüller Interface GmbH & Co.
KG - Detmold. All rights reserved. Duplication,
editing, distribution and any form of
exploitation, also as excerpts, is prohibited.
Subject to technical amendments
Note that this document may not always be
updated at the same time as technological
developments. Information and specifi cations
may change. Please check for the latest
version at www.weidmueller.de.
Disposal
Please observe national regulations! )
If disposing of individual parts, please do so
in accordance with their nature and existing
country-specifi c regulations, for example as:
• Electrical scrap
• Plastics
• Metals
Or, task a certifi ed disposal business with the
scrapping.
Relevant laws, applied standards and
directives
The laws, standards and directives for the device
applied by Weidmüller Interface GmbH & Co. KG
can be found in the declaration of conformity.
5 86
4
Energy Logger D550
Quick Guide
Supplement to the operating manual
Installation
Communication settings via Ethernet
"ecoExplorer go“ software settings (see link and QR code)
Brief description of device Assembly
The device
• is a data logger, as the basis for your energy
management.
• is designed for fi xed installation (mounting
rails) in low voltage switchgear.
• records and saves meter values and process
data.
The captured data serves to enable
• Evaluation of energy consumption and
operating hours.
• Monitoring switching statuses and faults in
buildings and operations.
The device is intended for weatherproof, fi xed
installation in low-voltage switchgear (protection
class II per IEC 60536).
• It is assembled on a 35 mm mounting rail in
accordance with DIN 60715.
• It can be installed in any mounting position.
• Forced ventilation is not required.
NOTE!
More detailed information on the device functions, data and installation can be found
in the operating manual.
DC connection variants
In order to parameterise all functions of the
device, you require a PC with the network
analysis software "ecoExplorer go" installed on
it (availability see front page).
Using the Modbus protocol, you can modify and
call up the data using the Modbus address list.
The Modbus address list can be found under
www.weidmueller.de.
In order to parameterise the device with the
software, connect your PC with the device via
the serial interface RS485, or via Ethernet.
PC
Energy Logger
D550
Ethernet
(crossover patch cable)
Direct connection of PC and Energy Logger D550 via Ethernet.
1.
2.
Connection of the Energy Logger D550 via Ethernet and a switch.
Ethernet Ethernet
Switch/Router
4.
(gedrehtes Patchkabel)
RS232
RS232
RS485
Connection of the Energy Logger
D550 via interface converter.
RS485
RS485
(gedrehtes Patchkabel)
Energy Meter
750
3.
Energy Analyser
D550
Connection of the Energy Meter D550
via an Energy Analyser D550 as gateway.
Ethernet RS485
RS485
(gedrehtes Patchkabel)
Energy Meter
D370
(Modbus slave)
5.
Energy Logger
D550
(gateway)
Connection of the Energy Logger
D550 with gateway function to the
PC via Ethernet.
PC
Ethernet
RS485
RS485
Energy Meter
D650
(Modbus slave)
The most common PC connection variants
between device and PC:
6.
Connection of the Energy Logger
D550 as Modbus-Slave device.
PC
Ethernet
RS485
RS485
Energy Analyser
D550
(Modbus Master)
RS485
Ethernet
In this connection variant, the
• Energy Logger D550 can forward on requests
(e.g. from the software) to a Modbus-Slave
device.
• Energy Logger D550 cannot independently
request Modbus-Slave devices itself!
RS485 mode:
Energy Logger D550 as gateway, address 3 = 1
(You can confi gure the address with the
"ecoExplorer go" software).
In this connection variant
• Communication with the Energy Logger D550
takes place via Ethernet or the Modbus Master.
• The Energy Logger D550 cannot transfer
Ethernet requests to further Modbus-Slave
devices itself!
RS485 mode:
Energy Logger D550 as Slave, address 3 = 0 (you
can confi gure the address with the "ecoExplorer
go" software).
Connecting the supply voltage
m
CAUTION!
Damage to property due to
disregard of the connection
conditions or impermissible
overvoltage
Your device can be damaged or destroyed
by a failure to comply with the connection
conditions or by exceeding the permissible
voltage range.
Before connecting the device to the supply
voltage, please check:
• Voltage and frequency correspond to the
details on the ratings plate! Threshold
value stipulated in the operating manual
have been complied with!
• In building installations, the supply voltage
must be protected with a UL approved
circuit breaker / a fuse (6 A, char. B)!
• The isolation device
- must be installed near the device and
in a location that is easily accessible
for the user.
- must be labelled to identify the
respective device.
• Provide a fuse for the neutral conductor
if the neutral conductor terminal of the
source is not grounded.
Circuit breaker
Fuse
The supply voltage for the device is
implemented via a 2-pole plug-in terminal.
The supply voltage level and frequency for your
device is specifi ed on the rating plate.
-
+
DC
AC
L
N
c
WARNING!
Danger of injury due to
electrical voltage!
Serious bodily injury or death can result from:
• Contact with bare or stripped live wires.
• Device inputs that are dangerous to touch.
Render your device free of voltage before
starting work! Check the system is free of
electrical energy!
Circuit breaker
Fuse
L
N
Fig. Connection of the supply voltage
via an external mains supply.
Fig. Connection of the supply
voltage.
Connections and control elements of the Energy Logger D550
Digital inputs group 1
Digital inputs group 2
Digital inputs group 3
Digital outputs
DIP switch S1,
device termination
RS485 interface
Rotary switch X10
Rotary switch X1
Ethernet interface
Battery compartment
Connection
Supply voltage
Service button S2
Thermistor input
m
CAUTION!
Property damage due to incorrect network settings
Incorrect network settings can cause faults in the IT network!
Find out the network settings for your device from your network administrator.
7
Ethernet interface
The Ethernet network settings are to be
specifi ed by the network administrator and set
accordingly on the Energy Logger D550 using the
"ecoExplorer go" software.
Ethernet connection
with the PC/switch
NOTE!
The Energy Logger D550 is factory-set
to the fi xed IP address 10.10.10.200
(subnet mask 255.0.0.0, DHCP =
deactivated).
The dynamic IP address is confi gured
via a direct Ethernet connection with the
software (see step 14, 15 and 16).
Within an Ethernet network, each device has
a unique TCP/IP address that can be set
manually or assigned by a DHCP server.
Fixed IP address
In networks without a DHCP server, the network
address of the device must be set via Modbus
or the software.
BootP
• Allows for the automatic integration of the
device in an existing network.
• Does not have the scope of functions of DHCP.
DHCP mode
DHCP integrates the Energy Logger D550
in an existing network with DHCP server
automatically. When started, the device pulls the
IP address, the network mask and the gateway
from the DHCP server.
17
16
10
Direct PC connection of the Energy Logger D550 via Ethernet (Windows 7)
A common way in which to integrate the Energy
Logger D550 in your PC network is direct
connection via the Ethernet interface.
NOTE!
Because the Energy Logger D550 is
supplied with a fi xed IP address, and
in order to integrate it in your company
network/your PC, you require administrator
rights for the following steps!
Fixed IP address of your Energy Logger
D550 (standard factory settings)
IP address 10.10.10.200
Subnet mask 255.0.0.0
DHCP deactivated
Set the IP address of your PC for the
connection with the Energy Logger D550:
1. Press the Windows key.
2. The "Start menu" appears.
3. Click on "Control panel" in the right menu
fi eld.
4. The window "Adjust your computer's
settings" appears.
5. Click on "Network and sharing center".
6. The "Network and sharing center" window
appears.
Fig.
MS-Windows 7 -
window
"Status of LAN
connection"
7. Click on "LAN connection" under the
internet heading.
8. The "LAN connection status" window
appears.
Fig. MS Windows 7 - "Network and sharing center"
window
9. Click on the "Properties" button.
10. After entering the administrator data, the
"Properties of LAN connection" window
appears.
Fig.
MS-Windows 7 -
window
"Properties of LAN
connection"
11. Double-click on "Internet protocol version 4
(TCP/IPv4)" to open the window "Properties
of internet protocol version 4 (TCP/IPv4)".
Fig.
MS-Windows 7 -
window
"Properties of
internet protocol
version 4 (TCP/
IPv4)"
12. Select the option "Use the following IP
address" and enter the fi xed IP address
and subnet mask. Please note that the IP
address of the PC must differ from the
fi xed IP address of the device in the 4th
number block (see fi gure above)!
13. Click on the "OK" button.
The Energy Logger D550 can now be confi gured
using the software installed on the PC!
6. In the selection list "Connection Type" >
"Ethernet" click on the "Address" fi eld and
enter the IP address of your device (fi xed IP
address 10.10.10.200), and enter the value of
the rotary switch of the Energy Logger D550
in the "Device Address" fi eld (in this case "1",
see step 7).
7. Click on the "Connection Test" button.
8. If the connection test is successful, the
"Display device information" window appears
with the serial number, hardware version and
fi rmware version.
9. Click on the "OK" button.
10. Exit the "Add new device to the project"
step by clicking on the "Done" button.
11. Confi gure your device (see following steps).
"ecoExplorer go" software settings for direct PC connection via Ethernet
Install the "ecoExplorer go" software on your
computer and proceed as follows:
Create a new project:
1. Select "File" >
"New project". For existing projects, select
your project under "File" > "Open project".
2. The "New project" window appears.
3. Click the "Next" button under step 1 "Select
project".
4. Under step 2 "Project path", select the:
- "Project name".
- "Project path".
5. Click on the "Done" button.
6. Your project appears on the left in the
"Projects" window in the working area.
Enter the new device into the project:
1. Select "File" >
"New fi le".
2. The "New fi le" window appears.
3. Under step 1 "Select fi le type" in the
category "Data logger" select the "File type"
"Energy Logger D550".
4. Click on the "Next" button.
5. The "Confi gure connection" step appears
in the window.
IP confi guration of the Energy Logger D550 ("ecoExplorer go") via direct
PC connection
NOTE!
In order to integrate the Energy Logger
D550 in a network with DHCP server
and for automatic assignment of the
IP address, subnet mask and gateway,
change the IP confi guration from "Fixed
IP Address" (standard setting) to "DHCP
Mode". To do so, fi rst set a "PC direct
connection with Energy Logger D550
via Ethernet" and confi gure the "DHCP
Mode"!
Once you have connected the Energy Logger
D550 with your PC via Ethernet (see step 15) and
integrated it in the "ecoExplorer go" software:
1. Open the context menu for your device with
the right mouse button:
In the window "Projects" > "Your project"
> "Devices" > "By device type" > "Energy
Logger D550" > "Device x".
2. Click on the "Confi guration" menu item in the
context menu.
3. The "Confi guration [device x]" window appears
in the right half of the working area.
PC connection of the Energy Logger D550 via Energy Analyser D550 as gateway
1. Confi gure your Energy Analyser D550 via
Ethernet cable on your PC as a "DHCP
Client" (device IP address is assigned
automatically, see operating manual and
quick guide to the device).
2. Connect your Energy Logger D550 via the
RS485 interface with the Energy Analyser
D550.
NOTE!
In order to integrate the Energy Logger
D550 in a network with DHCP server and
automatic assignment of the IP address,
subnet mask and gateway, change the
IP confi guration from"Fixed IP Address"
(standard setting) to "DHCP Mode" in the
"ecoExplorer go" software.
Ensure that the Baud rates of the devices
match up in the RS485/bus structure!
"ecoExplorer go" software
Install the software on your computer and
proceed as follows:
1. Open the software on your PC.
2. Select "File" >
"New project". For existing projects, select
your project under "File" > "Open project".
3. The "New project" window appears.
4. Click the "Next" button under step 1
"Select project".
5. Under step 2 "Project path", select the:
- "Project name".
- "Project path".
6. Click on the "Done" button.
7. Your project appears on the left in the
"Projects" window in the working area.
Add Energy Analyser D550 to the project:
1. Select "File" > "New fi le" in the menu bar.
2. The "New fi le" window appears.
3. Under step 1 "Select fi le type" in the
category "Measurement devices" select the
"File type" (Energy Analyser D550).
4. Click on the "Next" button.
6. Select "Connection type" > "TCP/IP" in the
selection list and enter the IP address of
your device in the "Host" fi eld.
The IP address of your Energy Analyser
D550 is determined via the addresses 300
to 303 in programming mode (see operating
manual and quick guide to the device).
7. Click on the "Connection Test" button.
5. The "Confi gure connection" step appears
in the window.
Add Energy Logger D550 to the project:
1. Click in the project window on the plus symbol in
front of the "Devices" directory.
2. Click in the "Devices" directory on the plus symbol in
front of the "By device type" subdirectory.
3. The previously installed Energy Analyser D550
appears.
4. Right-click with the mouse on the subdirectory
"By device type".
5. Click on the "New" menu item in the context menu.
6. Click on the "Other" menu item in the sub-menu.
7. The "New fi le" window appears.
8. If the connection test is successful, the
"Display device information" window
appears with the serial number, hardware
version and fi rmware version.
9. Click on the "OK" button.
10. Exit the "Add new device to the project"
step by clicking on the "Done" button.
8. Under step 1 "Select fi le type" in the
category "Data logger" select the fi le type
"Energy Logger D550".
9. Click on the "Next" button.
10. The "Confi gure connection" step appears
in the window.
11. In the selection list "Connection type" >
"Ethernet gateway", in the fi eld "Address",
set the IP address of your Master device
(Energy Analyser D550) and as the device
address apply the device address (rotary
switch) set on the Energy Logger D550 (1).
12. Click on the "Connection Test" button.
13. If the connection test is successful, the
"Display device information" window
appears with the serial number, hardware
version and fi rmware version.
NOTE!
Please make sure that the device
addresses of the Master (Energy Analyser
D550) and Slave (Energy Logger D550)
differ from each other. The device address
of the Master (device ID of the Energy
Analyser D550) is confi gured in the
window "Confi guration" > Menu "Serial
interface" in the software.
14. Click on the "OK" button.
15. Exit the "Add Energy Logger D550 to the
project" step by clicking on the "Done"
button.
16. You can now confi gure your device with the
software.
14
4. In the "Confi guration" window under the
"IP confi guration" menu, in the selection
list "DHCP Mode" select > DHCP.
5. End the process by clicking on the
"Transfer" button.
Your Energy Logger D550 is now prepared for
automatic integration in a network with DHCP
server.
RS485 interface
The RS485 interface on the device
• is designed as a 2-pole plug contact.
• communicates via Modbus RTU protocol.
The user-friendly confi guration of the device is
possible with the "ecoExplorer go" software.
RS485 bus structure
• In an RS485 bus structure (line), you connect
all devices in accordance with the Master-
Slave principle.
• One segment of an RS485 bus structure can
include up to 32 subscribers/devices.
• The cable is terminated with termination
resistors (120 Ω, 0.25 W) at the beginning and
end of a bus structure. The device contains
a termination resistor, which can be activated
via DIP switch S1.
• With more than 32 subscribers, repeaters
(amplifi ers) are used to connect bus segments.
• Voltage must be present at devices with an
active termination resistor.
• Recommendation: Install the Master at the end
of a bus segment.
• If the Master device is replaced with
a termination resistor that is active, the bus
structure is out of operation.
• Replacing a Slave device with a bus
connection that is either switched on or de-
energised can destabilise the bus structure.
• Devices without a bus connection can be
replaced without this having an effect on the
bus structure.
Device address (RS485)
Example
Device address 13
Factory setting
Device address 1
0
1
2
4
6
7
5
3
8
9
0
1
2
4
6
7
5
3
8
9
0
1
2
4
6
7
5
3
8
9
0
1
2
4
6
7
5
3
8
9
DIP switch S1, LED device status
DIP switch S1
Depending on the placement of the Energy
Logger D550 in a bus structure, it is possible to
activate the integrated bus termination resistor
via the DIP switch S1 (see step 9).
LED device status
2 LED lights beneath the RS485 interface
indicate the status of the device:
Both LEDs light up. The device is
performing the start process.
2 LEDs - device status
After 15 seconds, the start procedure is
complete. The red LED goes out, the green
LED lights up and indicates "Device in
operation".
Fig. Bus structure
Speisung notwendig / power supply necessary
Busabschluß eingeschaltet / bus terminator on
T
SlaveSlaveSlave
Slave Slave Slave Repeater
Slave Slave Slave Slave
Master
T
T
T
T
Baud rate
Confi gure a common Baud rate for devices in
an RS485 bus structure.
The Baud rate for the Energy Logger D550 is
confi gured via software or address 002 of the
Modbus address list.
Address 002
Setting
Baud rate
0 9.6 kbps
1 19.2 kbps
2 38.4 kbps
3 57.6 kbps
4 115.2 kbps (factory setting)
Modbus address 004 is used to confi gure the
number of stop bits where 0=1 stop bit (factory
setting) and 1=2 stop bits.
Data bits (8) and parity (none) are preset.
Digital inputs and outputs S0 pulse input/S0 pulse transducer Thermistor input
Digital inputs
The device has 15 digital inputs.
The digital inputs are divided into 3 groups, each
with 5 inputs:
• 5 inputs share one joint earth respectively.
• LEDs indicate the status of the inputs. If the
LED lights up (green) then a signal is present
at this input.
• An input signal is present (signal "1")
if a voltage of at least 18 V is fl owing
at a digital input (typically 4 mA at 24 V).
• If the input voltage is <5 V DC, no input signal
is present (signal "0").
NOTE!
For fault-free operation of the device:
• Lay screened cable from a cable
length from 30 m.
• Correct polarity of the supply
voltage for the digital inputs
(20 - 30 V DC) must be ensured.
Group 1 Group 2
LED Function
Yellow
Lights up when a connection (link)
exists.
Green
Lights up sporadically when network
activity occurs.
Example connection "Digital inputs of groups
1 and 2"
6
5
4k
Digital
Input 5
4
4k
Digital
Input 4
3
4k
Digital
Input 3
2
4k
Digital
Input 2
1
4k
Digital
Input 1
3,9V
3,9V
3,9V
3,9V
3,9V
Energy Logger D550
Digital inputs 1-5
-
+
24V DC
S5
S4
External
auxiliary voltage
S3
S2
S1
Example of the connection of external switch
contacts S1 to S5 to digital inputs 1 to 5.
Digital outputs
The device features 3 digital outputs that use a joint
earth:
• The LEDs indicate the status of the outputs.
If the LED lights up (red) then the output is set
to active - irrespective of whether there is an
onwards connection to this output.
• Digital output 1 can be confi gured to monitor the
temperature. It is connected with a comparator
via the thermistor input.
The digital outputs:
• can be switched via Modbus and the weekly
switch clock.
• can display the results of comparators.
• require external auxiliary voltage.
• can be used as pulse outputs.
• switch AC and DC loads.
• are not short circuit-proof.
Fig. Connection
Digital/pulse outputs
K2 K1
24 V
AC/DC
External
auxiliary voltage
Energy Logger D550
Digital outputs 1-3
Digital outputs 1-3
22
Digital
Output 1
23
Digital
Output 2
21
-+
DC
DC
24
Digital
Output 3
Example DC connection of two relays
at the digital outputs
NOTE!
• If you use digital outputs as pulse
outputs then the residual ripple of the
external auxiliary voltage (DC) must
not exceed max. 5%.
• Digital outputs are not short-circuit
proof!
NOTE!
The user-friendly confi guration of the
digital inputs and outputs of the Energy
Logger D550 takes place in the software.
NOTE!
In order to avoid data loss, save your
device confi guration changes with the
"Transfer" or "Transfer to" buttons!
NOTE!
This device confi guration represents
the basic settings. Further details for
device settings required for different
functions can be found in the operating
manual (available online) for the
software.
Fig.: S0 plug-in module
for connecting S0 pulse
transducers
Each digital input of the device is designed
for the connection of an S0 pulse transducer.
This requires an external auxiliary voltage with
an output voltage in the range of 20 - 27 V DC
and a resistor of 1.3 kOhm/1 W.
The S0 plug module
(optional):
• enables simple and fast connection of S0
pulse transducers.
• is for a group of 5 inputs with integrated
resistors.
6
5
4k
Digital
Input 5
4
4k
Digital
Input 4
3
4k
Digital
Input 3
2
4k
Digital
Input 2
1
4k
Digital
Input 1
3,9V
3,9V
3,9V
3,9V
3,9V
Energy Logger D550
Digital inputs 1-5
-
+
24V DC
External
auxiliary voltage
S0
Pulse
transducer
1.3 k/1 W
Fig.: PT1000 line connection
25
26
27
Example:
3-line connection PT100
25
26
27
Example:
2-line connection PT1000
(requires additional bridge)
25
26
27
Example:
2-line connection KTY83
(requires additional bridge)
k
a
When connecting the KTY83/84 sensor, correct
polarity must be ensured! Connect the negative
connection (labelled with a black ring) to
terminal 25!
The thermistor input on the device is
dimensioned for a temperature sensor with a
resistance range of 400 Ω to 4 kΩ. Do not exceed
the total resistance load (sensor + cable) of 4 kΩ!
The device determines the temperature
measurement value once per second.
Confi gure the sensor type and temperature
offset with the software or via Modbus.
The most important technical data
Supply voltage
Installation overvoltage
category
300 V CAT II
Protection of the supply
voltage (fuse)
Fuse:
6 A, Char. B (per UL/IEC)
Nominal range
AC 20 V - 250 V (45 - 65 Hz) or
DC 20 V - 300 V
Power consumption max. 4 VA / 2 W
Digital inputs
15 digital inputs, semiconductor relays, not short-circuit proof.
Supply voltage
20 V - 30 V DC
(SELV or PELV supply)
Input signal present
(signal "1")
> 18 V DC (typical 4 mA at 24 V)
Input signal not present
(signal "0")
< 5 V DC
Pulse input (S0), maximum
count frequency
25 Hz
Pulse input
1)
per DIN EN 62053-31:1998
(IEC 62053-31:1998 Class B)
1) To operate the device in accordance with DIN EN 65053-31
(S0), a resistor (1.3 kΩ/1 W) must be connected parallel to
the input.
NOTE!
Further technical data can be found in
the operating manual for the device.
Digital outputs
3 digital outputs, semiconductor relays, not short-circuit proof.
Supply voltage
20 V - 30 V DC
(SELV or PELV supply)
Switching voltage max. 60 V DC
Switching current max. 50 mAeff DC
Pulse output
(energy pulses)
Max. 20 Hz
Pulse output
per DIN EN 62053-31:1998
(IEC 62053-31:1998 Class B)
Temperature measurement input, 1 input (3-wire measurement).
Update time 1 second
Connectable sensors PT100, PT1000, KTY83, KTY84
Total burden
(sensor + cable)
max. 4kΩ
9
10 11 12
13 15
Device error.
If both LEDs are still illuminated after
the start procedure is complete, the
initialisation process was interrupted.
Perform a device update (fi rmware) via the
software.
If multiple devices are connected with each other
via the RS485 interface (e.g. in a bus structure,
see section 9), the master device distinguishes
between the integrated devices on the basis of
the device address. Each device on a network is
therefore issued a different device address.
The device address of the Energy Logger D550
is confi gured via 2 rotary switches
• The setting range lies between 1 and 99.
• The device address 00 is reserved! Do not
assign for Modbus communication!
• The device address 99 is attained by setting
X10 = 9 and X1 = 9 (highest setting value).
X10 X1
A
B
S1
Fig.: Placement at the end of a bus structure;
termination via DIP switch S1 activated (ON, 120 Ω).
A
B
S1
Fig.: Placement in the middle of a bus segment;
termination via DIP switch S1 deactivated (OFF).
-
+
-
+
~
Artikel-Nr.: 242552 Energy Logger D550 ProData2
PC
PC
PC
www.weidmueller.com
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
+49 5231 14-0
+49 5231 14-292083
info@weidmueller.de
http://wmqr.eu/242552
Energy Logger
D550
Energy Logger
D550
Energy Logger
D550
Energy Meter
750
Energy Logger
D550
(Modbus slave)
Energy Meter
D370
(Modbus slave)
Energy Meter
D650
(Modbus slave)
2425820000/00/01.16
Deutsche Version:
siehe Vorderseite