Approval/Certificate/Document of Conformity
Annex 1 to: Certificate of Conformity IECEx KEM 09.0071X
Report NL/KEM/ExTR10.0041/02
Page 1 of 1
Form 124
Version 3 (2018-03)
DEKRA Certification B.V. Meander 1051, 6825 MJ Arnhem P.O. Box 5185, 6802 ED Arnhem The Netherlands
T +31 88 9683000 F +31 88 9683100 www.dekra-certification.com Registered Arnhem 09085396
Electrical data
Supply (terminals 51, 52): U = 19.2 ... 31.2 Vdc.
Digital input (terminals 41, 42 and 43, 44): U ≤ 60 Vdc
Status Relay (terminals 53, 54):
U ≤ 32 Vdc or 32 Vac, I ≤ 1 Adc or I ≤ 0.5 Aac respectively.
If the Solenoid / Alarm driver is installed outside the hazardous area, the following data for the relay contacts
apply: U ≤ 110 Vdc or 125 Vac, I ≤ 0.3 Adc or I ≤ 0.5 Aac respectively.
For all circuits above: Um = 253 Vac (max. frequency 400 Hz).
Solenoid / Alarm driver, Type ACT20X-SDI-HDO-L-S, Type ACT20X-SDI-HDO-L-P and Type ACT20X-
2SDI-2HDO-S, Type ACT20X-2SDI-2HDO-P, output circuits (terminals 11 ... 14 and 21 ... 24):
in type of protection intrinsic safety Ex ia IIC/IIB/IIA/IIIC/I, with following maximum values:
Uo = 28 V; Co = 80 nF (IIC) or 640 nF (IIB) or 2.1 µF (IIA) or 3.76 µF (I);
and for terminals 11, 12 and 21, 22:
Io = 93 mA; Po = 0.65 W; Lo = 4.2 mH (IIC) or 16.8 mH (IIB) or 32.6 mH (IIA) or 47 mH (I);
Lo/Ro = 54 µH/Ω (IIC) or 218 µH/Ω (IIB) or 436 µH/Ω (IIA) or 717 µH/Ω (I);
and for terminals 11, 13 and 21, 23:
Io = 100 mA; Po = 0.70 W; Lo = 3.5 mH (IIC) or 14.2 mH (IIB) or 27.6 mH (IIA) or 46 mH (I);
Lo/Ro = 50 µH/Ω (IIC) or 201 µH/Ω (IIB) or 402 µH/Ω (IIA) or 667 µH/Ω (I);
and for terminals 11 ... 14 and 21 ... 24:
Io = 110 mA; Po = 0.77 W; Lo = 2.9 mH (IIC) or 11.8 mH (IIB) or 22.8 mH (IIA) or 38 mH (I);
Lo/Ro = 46 µH/Ω (IIC) or 184 µH/Ω (IIB) or 369 µH/Ω (IIA) or 607 µH/Ω (I).
For group IIIC, the parameters of group IIB apply.
Solenoid / Alarm driver, Type ACT20X-SDI-HDO-H-S, Type ACT20X-SDI-HDO-H-P, output circuits
(terminals 11 ... 14):
in type of protection intrinsic safety Ex ia IIC/IIB/IIA/IIIC/I, with following maximum values:
Uo = 28 V; Co = 80 nF (IIC) or 640 nF (IIB) or 2.1 µF (IIA) or 3.76 µF (I);
and for terminals 11, 12:
Io = 115 mA; Po = 0.81 W; (group IIC IIC/IIB/IIA/IIIC/I);
Lo = 2.69 mH (IIC) or 10.8 mH (IIB) or 20.8 mH (IIA) or 33 mH (I);
Lo/Ro = 44 µH/Ω (IIC) or 176 µH/Ω (IIB) or 353 µH/Ω (IIA) or 578 µH/Ω (I);
and for terminals 11, 13:
Io = 125 mA; Po = 0.88 W; (group IIB/IIA/IIIC/I);
Lo = 9.1 mH (IIB) or 17.6 mH (IIA) or 28 mH (I);
Lo/Ro = 163 µH/Ω (IIB) or 327 µH/Ω (IIA) or 533 µH/Ω (I);
and for terminals 11 ... 14:
Io = 135 mA; Po = 0.95 W; (group IIB IIA/IIIC/I);
Lo = 7.80 mH (IIB) or 15.1 mH (IIA) or 24 mH (I);
Lo/Ro = 150 µH/Ω (IIB) or 301 µH/Ω (IIA) or 493 µH/Ω (I);
For group IIIC, the parameters of group IIB apply.
The intrinsically safe output circuits are infallibly galvanically isolated from the non-intrinsically safe circuits,
and from eachother if applicable.