User Documentation

SIL concept for DTMs
24 1482880000/01/11.2017
16.2 Verification procedure
The configuration is re-load from the device and shown in a DTM GUI (Graphical User Interface). The user
interface loaded the image (as image) with the loaded configuration in the same window. The user now sees
a GUI with the configuration loaded from the device, the entered configuration (device parameters) and the
stored image (written parameters) as a configuration and will be prompted to check the configuration.
The GUI for SIL configuration is continues read the SIL state and shall shown the change from “OPEN” to
“LOCK”, see Figure 6 "GUI SIL configuration (LOCK) (example)". If the configuration is corrupted, then the
devices rejected the configuration and change the state to “FAIL”. After successful locking the configuration
the user get a list of all parameter from the DTM and from the stored image file.
Figure 6: GUI SIL configuration (LOCK) (example)
If any parameter is found to be incorrect during verification deactivate the SIL state and go through the
configuration menu and correct the parameter(s). After the correction, activate the SIL state by entering the
password and confirm the password.