Approval/Certificate/Document of Conformity

IECEx Certificate
of Conformity
Certificate No: IECEx KEM 09.0071X Issue No: 2
Date of Issue: 2019-03-26
Schedule
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
Solenoid / Alarm driver, Type ACT20X-SDI-HDO-L-S, Type ACT20X-SDI-HDO-L-P, Type ACT20X-SDI-HDO-H-S, Type ACT20X-SDI-HDO-
H-Pand TypeACT20X-2SDI-2HDO-S, TypeACT20X-2SDI-2HDO-P for rail mounting are 24 V powered isolating barriers, converting digital
signals from PLC's and other equipment into signals for driving valves, solenoids and light emitting diodes located in a hazardous area.
Ambient temperature range -20 °C to +60 °C.
For electrical data, refer to the Annex to this certificate.
SPECIFIC CONDITIONS OF USE: YES as shown below:
The Solenoid / Alarm driver shall be installed in a controlled environment with suitable reduced pollution, limited to pollution degree 2 or
better.
The non-intrinsically safe circuits may only be connected to an overvoltage category I or II power source, as defined in IEC 60664-1.
If the Solenoid / Alarm driver is installed in an explosive atmosphere where the use of equipment protection level Gc is required, the Solenoid
/ Alarm driver shall be installed in an enclosure in type of protection Ex n or Ex e, providing a degree of protection of at least IP54.
Cable entry devices and blanking elements shall fulfil the same requirement.
Page 3 of