Functional specification of the non-safety functions
10 1482850000/01/11.2017
7. Functional specification of the non-safety functions
The status relay (terminal 53 and 54) and LED outputs are not suitable for use in any Safety Instrumented
Function. The displayed value in the FDT/DTM software and any possible parameterization by the FDT/DTM
software does not affect the safety function of the ACT20X-(2)SAI-(2)HAO. Also the HART transparency of
the device is not a safety function.