Approval/Certificate/Document of Conformity
IECEx Certificate
of Conformity
Certificate No: IECEx KEM 09.0092X Issue No: 2
Date of Issue: 2019-03-26
Schedule
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
Temperature / mA Converters Type ACT20X-HTI-SAO-S, Type ACT20X-HTI-SAO-P and Type ACT20X-2HTI-2SAO-S and ACT20X-2HTI-
2SAO-P), for rail mounting are 24 V powered 1 channel (Type ACT20X-HTI-SAO-S and Type ACT20X-HTI-SAO-P) or 2 channel (Type
ACT20X-2HTI-2SAO-S and Type ACT20X-2HTI-2SAO-P) isolating barriers, interfacing temperature sensors or current sources located in a
hazardous area.
Ambient temperature range -20 °C to +60 °C.
For electrical data, refer to the Annex to this certificate.
SPECIFIC CONDITIONS OF USE: YES as shown below:
The Temperature / mA Converter shall be installed in a controlled environment with suitable reduced pollution, limited to pollution degree 2 or
better.
The non-intrinsically safe circuits may only be connected to an overvoltage category I or II power source, as defined in IEC 60664-1.
If the Temperature / mA Converter is installed in an explosive atmosphere where equipment protection level Gc is required, the Temperature
/ mA Converter shall be installed in an enclosure in type of protection Ex n or Ex e, providing a degree of protection of at least IP54.
Cable entry devices and blanking elements shall fulfil the same requirements.
Page 3 of