Approval/Certificate/Document of Conformity

(13)
SCHEDULE
(14)
to EU-Type Examination Certificate KEMA 10ATEX0020X Issue No. 3
Page 3/3
Form 227A
Version 1 (2016-04)
(16)
Report
Number
KEMA NL/KEM/ExTR10.0015/02
(17)
Speci
fic
conditions
use
The Temperature / mA Converter shall be installed in a controlled environment with suitable
reduced pollution, limited to pollution degree 2 or better.
The non-intrinsically safe circuits may only be connected to an overvoltage category I or II power
source, as defined in EN 60664-1.
If the Temperature / mA Converter is installed in an explosive atmosphere where the use of
apparatus of equipment category 3 G is required, the following special conditions for safe use
apply:
The Temperature / mA Converter shall be installed in an enclosure in type of protection Ex n or
Ex e, providing a degree of protection of at least IP54.
Cable entry devices and blanking elements shall fulfil the same requirement.
(18)
Essential Health and Safety Requirements
Covered by the standards listed at item (9).
(19)
Test documentation
As listed in Test Report No. NL/KEM/ExTR10.0015/02.
(20)
Cert
i
ficate history
Issue 1 - 213256400 Initial certificate,
Issue 2 - 216740400 Update to new standards,
Issue 3 - 223250800 Addition of *–P models and removal of EN 60079-26.