User Documentation

SIL concept for DTMs
1482900000/01/11.2017 35
Selectable TC sensor types (for channel tag and type = TC):
type B
type E
type J
type K
type L
type N
type R
type S
type T
type U
type W3
type W5
type Lr
CJC type for (for channel tag and type = TC):
Internal CJC = internal CJC sensor measurement
External CJC = connector measurement (accessory)
Temperature unit
Selected temperature unit (for channel tag and type = current):
Celsius
Fahrenheit
Temperature limits
Selected temperature unit (for channel tag and type = temperature):
Low = selected temperature value for 0 % output (for channel tag and type
= temperature) for selected temperature unit (°C or °F). Range is defined
by the selected temperature sensor (TC-, Ni- or Pt-type), but value must be
less than high - minimum span.
High = Selected temperature value for 100 % output (for channel tag and
type = temperature) for selected temperature unit (°C or °F). Range is
defined by the selected temperature sensor (TC-, Ni- or Pt-type), but must
be larger than low + minimum span.
Output tab
Name
Function
Range
Fixed output range for current output:
Not valid when SIL is active (safety applications)
0...20 mA
20...0 mA
Valid when SIL is active (safety applications)
4...20 mA
20...4 mA
Action on Error
Fixed output value on detected sensor error:
No action = Sensor error detection NOT enabled, output at sensor error is
undefined.