Approval/Certificate/Document of Conformity
Annex 1 to: Certificate of Conformity IECEx KEM 09.0072X
Report NL/KEM/ExTR09.0087/03
Page 1 of 1
Form 124
Version 3 (2018-03)
DEKRA Certification B.V. Meander 1051, 6825 MJ Arnhem P.O. Box 5185, 6802 ED Arnhem The Netherlands
T +31 88 9683000 F +31 88 9683100 www.dekra-certification.com Registered Arnhem 09085396
Electrical data
Supply (terminals 51, 52): U = 19.2 ... 31.2 Vdc
Digital outputs (terminals 41, 42 and 43, 44):
Transistor output, Umax = 30 Vdc, Imax = 80 mA (Type ACT20X-HDI-SDO-…-S and Type ACT20X-HDI-
SDO-…-P)
Relay contacts, Umax = 30 Vdc or 32 Vac, Imax = 2 A (Types ACT20X-.HDI-.SDO-…-S and Types
ACT20X-.HDI-.SDO-…-P)
If the Pulse Isolator is installed outside the hazardous area, the following data for the relay contacts apply:
U ≤ 30 Vdc or 250 Vac, I ≤ 2 Adc or Aac respectively.
Status output (terminals 53, 54):
Relay contacts, U ≤ 32 Vdc or 32 Vac, I ≤ 1 Adc or I ≤ 0.5 Aac respectively.
If the Pulse Isolator is installed outside the hazardous area, the following data for the relay contacts apply: U
≤ 110 Vdc or 125 Vac, I ≤ 0.3 Adc or I ≤ 0.5 Aac respectively.
For all circuits above: U
m
= 253 Vac (max. frequency 400 Hz).
Sensor circuits (terminals 11 ... 14, 21 ... 24):
in type of protection intrinsic safety Ex ia IIC/IIB/IIA/IIIC/I, with following maximum values:
U
o
= 10.6 V; I
o
= 12 mA; P
o
= 32 mW; C
o
= 2.0 µF (IIC) or 6.0 µF (IIB) or 18.0 µF (IIA) or 90 µF (I);
L
o
= 260 mH (IIC) or 780 mH (IIB) or 1000 mH (IIA) or 1000 mH (I);
L
o
/R
o
= 1150 µH/Ω (all groups);
For group IIIC, the parameters of group IIB apply.
The intrinsically safe sensor circuits are infallibly galvanically isolated from each other and from the non-
intrinsically safe circuits.