Approval/Certificate/Document of Conformity
IECEx Certificate
of Conformity
Certificate No: IECEx KEM 09.0072X Issue No: 3
Date of Issue: 2019-03-25
Schedule
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
NAMUR Pulse Isolators, for rail mounting, Type ACT20X-.HDI-.SDO-...-S or Type ACT20X-.HDI-.SDO-...-Pare 24 Vpowered isolating
barriers, interfacing "Namur" sensors or contacts located in an explosive atmosphere.
ACT20X-HDI-SDO-...-S orACT20X-HDI-SDO-...-P are one channel versions.
ACT20X-2HDI-2SDO-...-S or ACT20X-2HDI-2SDO-...-P are two channel versions.
Ambient temperature range-20 °C to +60 °C.
Used models:
Type ACT20X-HDI-SDO-RNO-S,
Type ACT20X-HDI-SDO-RNO-P,
Type ACT20X-HDI-SDO-RNC-S,
Type ACT20X-HDI-SDO-RNC-P,
Type ACT20X-HDI-SDO-S,
Type ACT20X-HDI-SDO-P,
Type ACT20X-2HDI-2SDO-RNO-S,
Type ACT20X-2HDI-2SDO-RNO-P,
Type ACT20X-2HDI-2SDO-RNC-S,
Type ACT20X-2HDI-2SDO-RNC-P,
Type ACT20X-2HDI-2SDO-S,
Type ACT20X-2HDI-2SDO-P
For electrical data, refer to the Annex to this certificate.
SPECIFIC CONDITIONS OF USE: YES as shown below:
The NAMUR Pulse Isolator shall be installed in a controlled environment with suitable reduced pollution, limited to pollution degree 2 or
better.
The non-intrinsically safe circuits may only be connected to an overvoltage category I or II power source, as defined in IEC 60664-1.
If the NAMUR Pulse Isolator is installed in an explosive atmosphere where equipment protection level Gc is required shall be installed in an
enclosure in type of protection Ex n or Ex e, providing a degree of protection of at least IP54.
Cable entry devices and blanking elements shall fulfil the same requirements.