Approval/Certificate/Document of Conformity
[13] Schedule
[14] TYPE EXAMINATION CERTIFICATE No.
DEMKO 18 ATEX 2097X Rev. 1
00-IC-F0060-1 – Issue 15.1 This certificate may only be reproduced in its entirety and without any change, schedule included. Page 2 of 2
[15] Description of Product:
This device is an Analog temperature monitor, which contains two relay outputs, and a PTC sensor or PT100 input terminal blocks. When
the PT100 or PTC sensor's input temperature is over-temperature or under-temperature, the relay output changes. These units do not have
a complete electrical enclosure and must be placed into a separate enclosure in the final installation.
Nomenclature for type ACT20P-TMR-RTI-S and ACT20P-TMR-RTI-P:
ACT20P
-
TMR
-
RTI
-
S
1
2
3
4
1: Product series
- ACT20P
2: Product Function: Temperature Monitor and Relay output
- TMR
3: Input signal type: Pt100 sensor or PTC sensor
- RTI
4: Connection type: Screw or Push-In
- S: Screw connection
- P: Push-In connection
The optical radiation output of the product with respect to explosion protection, according to Annex II clause 1.3.1 of the Directive
2014/34/EU is covered in this certificate based on Exception 1 to the scope of EN 60079-28:2015.
Temperature range:
The ambient temperature range is -25 C ≤ Tamb ≤ +65C
Electrical data
Power input: 24~240 V ac/ V dc, 40~60Hz, Max. 2.2 W
Signal input: PT100/PTC sensor
Relay Output: 250 V ac, 5 A
Routine tests:
A dielectric strength routine test is required in accordance with EN 60079-15, clause 6.2. Alternatively, test shall be carried out at 1.2 times
the test voltage, but shall be maintained for at least 100ms.
[16] Descriptive Documents
The scheduled drawings are listed in the report no. provided under item no. [ 8 ] on page 1 of this Type Examination Certificate.
[17] Special Conditions of Use:
The equipment shall be installed in an enclosure that provides a degree of protection not less than IP 54 in accordance with EN 60079-0.
[18] Essential Health and Safety Requirements
The Essential Health and Safety Requirements (EHSRs) covered by the standards listed at item 9.
Additional information
The trademark will be used as the company identifier on the marking label.