Approval/Certificate/Document of Conformity
[13]
Schedule
[14] TYPE EXAMINATION CERTIFICATE No.
DEMKO 19 ATEX 2226X Rev. 0
00-IC-F0060-1 – Issue 15.1
This certificate may only be reproduced in its entirety and without any change, schedule included. Page 2 of 3
[15] Description of Product:
These devices are considered Open-Type Analogue Signal Converter, which can connect with current or voltage source signal. The signal
0/4 -20mA or 0-5/10V is isolated and transferred through output side.
Nomenclature for type ACT20P Series:
ACT20P
-
CI
-
CO
-
ILP
-
P
1
2
3
4
5
1: Product series:
ACT20P
2: Input signal:
CI: Type with one channel of 0/4~20mA current input
2CI: Type with two channels of 0/4~20mA current input
CI1: Type with one channel of 0~20mA current input
Cl2: Type with one channel of 4~20mA current input
VI1: Type with one channel of 0~5V voltage input
VI: Type with one channel of 0~10V voltage input
3: Output signal:
CO: Type with one channel of current output
2CO: Type with two channels of current output
4: Current loop type:
ILP: Input current loop power type
OLP: Output current loop power type
5: Input/Output connector type:
S: Type with screw connector
P: Type with push-in connector
Temperature range:
The ambient temperature range is -20 °C to +60 °C.
Electrical data
Model Supply Input Rating Input Signal Output Rating
ACT20P-2CI-2CO-ILP-P
ACT20P-2CI-2CO-ILP-S
ACT20P-CI-CO-ILP-P
ACT20P-CI-CO-ILP-S
12-30Vdc, input current loop
0/4~20 mA current source 0~20 mA or 4~20 mA
ACT20P-CI1-CO-OLP-P
ACT20P-CI1-CO-OLP-S
12-30Vdc, output current loop
0~20 mA current source 4~20 mA
ACT20P-CI2-CO-OLP-P
ACT20P-CI2-CO-OLP-S
ACT20P-CI-2CO-OLP-P
ACT20P-CI-2CO-OLP-S
12-30Vdc, output current loop
4~20 mA current source 4~20 mA
ACT20P-VI1-CO-OLP-P
ACT20P-VI1-CO-OLP-S
12-30Vdc, output current loop 0~5 V Voltage source 4~20 mA
ACT20P-VI-CO-OLP-P
ACT20P-VI-CO-OLP-S
12-30Vdc, output current loop 0~10 V Voltage source 4~20 mA
Routine tests:
N/A
[16] Descriptive Documents
The scheduled drawings are listed in the report no. provided under item no. [ 8 ] on page 1 of this Type Examination Certificate.
[17] Special Conditions of Use:
• The equipment shall be installed in an tool removable enclosure that provides a degree of protection not less than IP 54 in
accordance with EN 60079-0.
• The equipment shall only be used in an area of at least pollution degree 2, as defined in EN 60664-1.
• Transient protection shall be provided that is set at a level not exceeding 140 % of the peak rated voltage value at the supply
terminals to the equipment
[18] Essential Health and Safety Requirements
The Essential Health and Safety Requirements (EHSRs) covered by the standards listed at item 9.